WAGO-I/O-SYSTEM 750 XTR
Connect Devices
37
750-559/040-000 4AO 0-10V DC /XTR
Manual
Version 1.3.0
6
Connect Devices
Do not apply any voltage to the outputs!
Never connect the outputs to external voltage sources. Also, do not connect the
outputs to each other.
Failure to observe these measures can damage the product!
6.1
Connecting a Conductor to the CAGE CLAMP
®
The WAGO CAGE CLAMP
®
connection is appropriate for solid, stranded and
finely stranded conductors.
Only connect one conductor to each CAGE CLAMP
®
!
Only one conductor may be connected to each CAGE CLAMP
®
.
Do not connect more than one conductor at one single connection!
If more than one conductor must be routed to one connection, these must be
connected in an up-circuit wiring assembly, for example using WAGO feed-
through terminals.
1.
For opening the CAGE CLAMP
®
insert the actuating tool into the opening
above the connection.
2.
Insert the conductor into the corresponding connection opening.
3.
For closing the CAGE CLAMP
®
simply remove the tool. The conductor is
now clamped firmly in place.
Figure 10: Connecting a Conductor to a CAGE CLAMP
®