30
Device Description
WAGO-I/O-SYSTEM 750 XTR
750-559/040-000 4AO 0-10V DC /XTR
Manual
Version 1.3.0
Table 18: EMC
– Immunity to Interference
Standard
Test Value
Line Frequency Disturbances
• EN 60255-26
Standard not applicable
Alternating Components of the Voltage to DC Line Connections
• EN 61000-4-17
• EN 60255-26
15 %
Damped Oscillatory Waves
• EN 61000-4-18
• EN 60255-26
• IEEE C37.90.1
1.25 kV conductor/conductor
2.5 kV conductor/ground
Voltage Dips, Short-term Interruptions and Voltage Fluctuations to DC Supply
Inputs
• EN 61000-4-29
• EN 60255-26
Standard not applicable
Harmonics
• Shipbuilding
*)
Standard not applicable
*)
The list of ship certifications issued is available in the section “Approvals”.