Manual 

 

 

 

 

WAGO-I/O-SYSTEM 750 

2DO 230V AC 0.3A/SSR 

750-509  

2-Channel Digital Output Module 230 VAC/DC,  

with Solid State Relay 0.3 A 

Version 1.1.0  

 
 
 

 

Содержание 750-509

Страница 1: ...Manual WAGO I O SYSTEM 750 2DO 230V AC 0 3A SSR 750 509 2 Channel Digital Output Module 230 VAC DC with Solid State Relay 0 3 A Version 1 1 0...

Страница 2: ...1 8 87 5 55 Fax 49 0 571 8 87 85 55 E Mail support wago com Every conceivable measure has been taken to ensure the accuracy and completeness of this documentation However as errors can never be fully...

Страница 3: ...r Jumper Contacts Field Supply 16 3 2 3 CAGE CLAMP Connectors 18 3 3 Display Elements 19 3 4 Schematic Diagram 20 3 5 Technical Data 21 3 5 1 Device 21 3 5 2 Power Supply 21 3 5 3 Communication 21 3 5...

Страница 4: ...for America According to NEC 500 41 7 2 Installation Regulations 42 7 2 1 Special Conditions for Safe Use ATEX Certificate T V 07 ATEX 554086 X 43 7 2 2 Special Conditions for Safe Use ATEX Certifica...

Страница 5: ...anual and in the manual for the used fieldbus coupler controller Consider power layout of the WAGO I O SYSTEM 750 In addition to these operating instructions you will also need the manual for the used...

Страница 6: ...a moderate risk potentially hazardous situation which if not avoided could result in death or serious injury Personal Injury Indicates a low risk potentially hazardous situation which if not avoided m...

Страница 7: ...M 750 Notes about this Documentation 7 750 509 2DO 230V AC 0 3A SSR Manual Version 1 1 0 Additional Information Refers to additional information which is not an integral part of this documentation e g...

Страница 8: ...les are marked in italic type e g C Program Files WAGO Software Menu Menu items are marked in bold letters e g Save A greater than sign between two names means the selection of a menu item from a menu...

Страница 9: ...with the current norms and guidelines for the devices and automated environments All changes to the coupler or controller should always be carried out by qualified personnel with sufficient skills in...

Страница 10: ...system in a housing or switch cabinet 2 1 4 Technical Condition of Specified Devices The devices to be supplied ex works are equipped with hardware and software configurations which meet the individua...

Страница 11: ...ment and fixtures to authorized qualified staff only by means of specific keys or tools Replace defective or damaged devices Replace defective or damaged device module e g in the event of deformed con...

Страница 12: ...tion lines Avoid reverse polarity of data and power supply lines as this may damage the devices involved Avoid electrostatic discharge The devices are equipped with electronic components that may be d...

Страница 13: ...isolated i e the potential for the field supply touches one of the relay contacts 0 V 230 V AC DC When a relay is closed the field potential applied is then routed to the associated second relay conta...

Страница 14: ...re View Pos Description Details See Section 1 Marking possibility with Mini WSB 2 Status LEDs Device Description Display Elements 3 Data contacts Device Description Connectors 4 CAGE CLAMP connectors...

Страница 15: ...ich are available as self cleaning gold spring contacts Figure 2 Data Contacts Do not place the I O modules on the gold spring contacts Do not place the I O modules on the gold spring contacts in orde...

Страница 16: ...he contacts on the left side of the I O module are designed as male contacts and the contacts on the right side as spring contacts Figure 3 Power Jumper Contacts Table 4 Legend for Figure Power Jumper...

Страница 17: ...1 0 Do not exceed maximum current via power jumper contacts The maximum current to flow through the power jumper contacts is 10 A Greater currents can damage the contacts When configuring your system...

Страница 18: ...Table 5 Legend for Figure CAGE CLAMP Connectors Channel Designation Connector Function 1 DO 1 1 Output DO 1 Signal voltage 230 V 2 Output DO 1 Field supply N 3 Output DO 1 Neutral conductor Ground 4...

Страница 19: ...3 Display Elements Figure 5 Display Elements Table 6 Legend for Figure Display Elements Channel Designation LED State Function 1 Status DO 1 A Off Output DO 1 Signal voltage 0 Green Output DO 1 Signal...

Страница 20: ...20 Device Description WAGO I O SYSTEM 750 750 509 2DO 230V AC 0 3A SSR Manual Version 1 1 0 3 4 Schematic Diagram Figure 6 Schematic Diagram...

Страница 21: ...witching voltage 0 V 230 V AC DC Switching current 300 mA Isolation 1 5 kV eff field system rated impulse voltage 2 5 kV Overvoltage category III 3 5 3 Communication Table 9 Technical Data Communicati...

Страница 22: ...ta Data Contacts Data contacts Slide contact hard gold plated self cleaning 3 5 6 Climatic Environmental Conditions Table 14 Technical Data Climatic Environmental Conditions Operating temperature rang...

Страница 23: ...rmation on automation products WAGO I O SYSTEM 750 System Description The following approvals have been granted to 750 509 I O modules Conformity Marking CULUS UL508 Korea Certification MSIP REM W43 D...

Страница 24: ...nted to 750 509 I O modules ABS American Bureau of Shipping Federal Maritime and Hydrographic Agency BV Bureau Veritas DNV Det Norske Veritas Class B GL Germanischer Lloyd Cat A B C D EMC 1 KR Korean...

Страница 25: ...odules meet the following requirements on emission and immunity of interference EMC CE Emission of interference acc to EN 61000 6 4 EMC CE Immunity to interference acc to EN 61000 6 2 EMC marine appli...

Страница 26: ...s or their variants in the process image depends on the fieldbus coupler controller used Please take this information from the section Fieldbus Specific Design of the Process Data included in the desc...

Страница 27: ...odules with power contacts blade contacts cannot be linked to I O modules with fewer power contacts Risk of injury due to sharp edged blade contacts The blade contacts are sharp edged Handle the I O m...

Страница 28: ...le so that the tongue and groove joints to the fieldbus coupler controller or to the previous or possibly subsequent I O module are engaged Figure 7 Insert I O Module Example 2 Press the I O module in...

Страница 29: ...anual Version 1 1 0 5 2 2 Removing the I O Module 1 Remove the I O module from the assembly by pulling the release tab Figure 9 Removing the I O Module Example Electrical connections for data or power...

Страница 30: ...connected in an up circuit wiring assembly for example using WAGO feed through terminals Exception If it is unavoidable to jointly connect 2 conductors then you must use a ferrule to join the wires t...

Страница 31: ...on Examples 6 2 1 2 Wire Connection Protection Class I Actuators Figure 11 Connection Example 2 Wire Connection for Protection Class I Actuators 6 2 2 2 Wire Connection Protection Class II Actuators F...

Страница 32: ...6 2 3 3 Wire Connection Protection Class I Actuators Figure 13 Connection Example 3 Wire Connection for Protection Class I Actuators 6 2 4 3 Wire Connection Protection Class II Actuators Figure 14 Con...

Страница 33: ...ful in practice Table 16 Protective Circuits for Contacts of Relay Modules Protective Circuits Additional Off Delay Defined Induction Voltage Limitation Bipolar Effective Attenuation Advantages and Di...

Страница 34: ...Protective Circuits Additional Off Delay Defined Induction Voltage Limitation Bipolar Effective Attenuation Advantages and Disadvantages Figure 19 R C Combination medium to short no yes Advantages HF...

Страница 35: ...is designed for use in Zone 2 hazardous areas The following sections include both the general identification of components devices and the installation regulations to be observed The individual subsec...

Страница 36: ...anual Version 1 1 0 7 1 Marking Configuration Examples 7 1 1 Marking for Europe According to ATEX and IEC Ex Figure 20 Side Marking Example for Approved I O Modules According to ATEX and IECEx Figure...

Страница 37: ...e enclosure without a dust layer Mining I Equipment group Mining M2 Category High level of protection Ex Explosion protection mark d Mb Type of protection and equipment protection level EPL Flameproof...

Страница 38: ...STEM 750 750 509 2DO 230V AC 0 3A SSR Manual Version 1 1 0 Figure 22 Side Marking Example for Approved Ex i I O Modules According to ATEX and IECEx Figure 23 Text Detail Marking Example for Approved E...

Страница 39: ...otection level EPL protection by enclosure ia Da Type of protection and equipment protection level EPL associated apparatus with intrinsic safety circuits for use in Zone 20 ib Db Type of protection a...

Страница 40: ...egory 3 Zone 2 equipment containing a safety device for a category 2 Zone 1 equipment Ex Explosion protection mark nA Gc Type of protection and equipment protection level EPL Non sparking equipment ia...

Страница 41: ...I O Modules According to NEC 500 Figure 25 Text Detail Marking Example for Approved I O Modules According to NEC 500 Table 19 Description of Marking Example for Approved I O Modules According to NEC 5...

Страница 42: ...0 3A SSR Manual Version 1 1 0 7 2 Installation Regulations For the installation and operation of electrical equipment in hazardous areas the valid national and international rules and regulations whic...

Страница 43: ...only be actuated when explosive atmosphere can be excluded 4 The connecting and disconnecting of the non intrinsically safe circuits is only permitted during installation for maintenance or for repair...

Страница 44: ...0 and EN 60079 1 and the degree of protection IP64 The compliance of these requirements and the correct installation into an enclosure or a control cabinet of the devices shall be certified by an ExNB...

Страница 45: ...only be actuated when explosive atmosphere can be excluded 4 The connecting and disconnecting of the non intrinsically safe circuits is only permitted during installation for maintenance or for repair...

Страница 46: ...0 and IEC 60079 1 and the degree of protection IP64 The compliance of these requirements and the correct installation into an enclosure or a control cabinet of the devices shall be certified by an ExC...

Страница 47: ...Only for use in LAN not for connection to telecommunication circuits G WARNING Use Module 750 642 only with antenna module 758 910 H For Couplers Controllers and Economy bus modules only The instructi...

Страница 48: ...gure 13 Connection Example 3 Wire Connection for Protection Class I Actuators 32 Figure 14 Connection Example 3 Wire Connection for Protection Class II Actuators Protective Insulation 32 Figure 15 Dio...

Страница 49: ...cal Data Communication 21 Table 10 Technical Data Outputs 21 Table 11 Technical Data Field Wiring 22 Table 12 Technical Data Power Jumper Contacts 22 Table 13 Technical Data Data Contacts 22 Table 14...

Страница 50: ...WAGO Kontakttechnik GmbH Co KG Postfach 2880 D 32385 Minden Hansastra e 27 D 32423 Minden Phone 49 5 71 8 87 0 Fax 49 5 71 8 87 1 69 E Mail info wago com Internet http www wago com...