Table 49: General module / channel parameters
Parameter
Value
Explanation
Process alarm:
User limit value
violation
Channel x (x = 0 … 7)
0 (false)
Falling below the lower or above the upper user
limit on the respective signal channel does not
lead to transmission of a process alarm. The
lower and upper user limits are set in another
attribute.
1 (true)
*)
Provided that the channel diagnostics of the
respective signal channel has been activated,
falling below the lower or above the upper user
limit leads to transmission of a process alarm.
No entry in the diagnostics database of the
station proxy is made. The lower and upper user
limits are set in another attribute.
Lower user limit
−32768
*)
… 32767
Based on the value range of the input signal, a
lower limit value of the input signal can be
specified that can lead to the abovementioned
event of a process alarm.
Upper user limit
−32768 … 32767
*)
Based on the value range of the input signal, an
upper limit value of the input signal can be
specified that can lead to the abovementioned
event of a process alarm.
*)