10.1 Configuration and Parameterization using a GSD
File with PROFIBUS DP and PROFINET IO
10.1.1 Configuration 8 AI 0(4)-20 mA, S.E.
10.1.1.1 PROFIBUS DP Fieldbus Coupler/Controller
750-333(/0xx-000), 750-833(/0xx-000)
When using the aforementioned PROFIBUS DP fieldbus devices, the process
image size is configured by selecting the corresponding GSD entry.
Table 44: Configuration PROFIBUS DP
GSD Entry
PI-Length/[byte]
Data Type
Inst.
Module
Submodule
I
O
750-496 8AI/0/4-20mA/SE
n/a
16
n/a
INT16
8
750-496 8AI/0/4-20mA/SE
RA
24
24
{UINT8, INT16}
PFC 750-496 8AI/0/4-20mA/
SE
n/a
n/a
n/a
n/a
10.1.1.2 PROFINET IO Fieldbus Coupler
750-370, 750-375(/025-000), 750-377(/025-000)
When using the aforementioned PROFINET IO fieldbus couplers, the process
image size is configured by selecting the corresponding GSD entry.
Table 45: Configuration 750-370
GSD Entry
PI-Length/[byte]
Data Type
Inst.
Module
Submodule
I
O
750-496 8AI, 0(4)-20 mA
n/a
16
n/a
INT16
8
750-496 8AI, 0(4)-20 mA, EM
24
24
{UINT8, INT16}
Table 46: Configuration 750-375(/025-000), 750-377(/025-000)
GSD Entry
PI-Length/[byte]
Data Type
Inst.
Module
Submodule
I
O
750-496 8AI,
0(4)-20 mA
INT16[8] I
16
n/a
INT16
8
{UINT8, INT16}[8] I/O
24
24
{UINT8, INT16}