4.4.4
Temperature Measurements (RTD & TC) with High
Resolution
4.4.4.1 Standard Format/Celsius
With the setting “High Resolution,” the I/O module converts the measured values
of the temperature sensors (RTDs or TCs) into temperature values and outputs
the conversion results in degrees Celsius to two decimal places.
The temperature values are represented in one word (16 bits) with a resolution of
one digit per 0.01 °C.
The numerical range used corresponds to the defined temperature range of −50
°C … +150 °C and is output accordingly as a process value in the range
−5000 … +15000.
Exception:
With
Type C
TC sensors, the defined temperature range
corresponds to 0 °C…+150 °C, i.e. 0…15000 as a process value.
Table 43: Temperature Measurement Setting with High Resolution Option – Standard Format/Celsius
Temperature
[°C]
Numeric Value
1)
Status Byte,
Hex.
Error LED
Range
Hex.
Dec.
≤
-60.01
0x8000
-32768
0x50
On
Underflow
-60.00
0xE890
-6000
0x41
On
Underrange
-50.01
0xEC77
-5001
-50.00
0xEC78
-5000
0x00
Off
Nominal
range
150.00
0x3A98
15000
150.01
0x3A99
15001
0x42
On
Overrange
160.00
0x3E80
16000
≥ 160.01
0x7FFF
32767
0x60
On
Overflow
1)
Process values below 0 are represented in binary form as the two’s complement.
Table 44: Type C TC Setting with High Resolution Option – Standard Format/Celsius
Temperature
[°C]
Numeric Value
1)
Status Byte,
Hex.
Error LED
Range
Hex.
Dec.
≤
-10.01
0x8000
-32768
0x50
On
Underflow
-10.00
0xFC18
-1000
0x41
On
Underrange
-0.01
0xFFFF
-1
0.00
0x0000
0
0x00
Off
Nominal
range
150.00
0x3A98
15000
150.01
0x3A99
15001
0x42
On
Overrange
160.00
0x3E80
16000
≥ 160.01
0x7FFF
32767
0x60
On
Overflow