![WAGO 750-489 Скачать руководство пользователя страница 50](http://html1.mh-extra.com/html/wago/750-489/750-489_manual_868450050.webp)
50 Process Image
WAGO-I/O-SYSTEM 750
750-489 4AI RTD/TC/Strain Gauge Ex i
Manual
Version 1.1.0, valid from FW Version 02
4.4.3.3 TC Type C – Standard Format/Celsius
Table 29: TC Type C Setting – Standard Format/Celsius
Temperature
[°C]
Numeric Value
1)
Status
Byte,
Hex.
Error
LED
Range
Binary
Hex.
Dec.
≤
-25.1
'1000.0000.0000.0000'
0x8000 -32768
0x50
On
Underflow
-25.0
'1111.1111.0000.0110'
0xFF06
-250
0x41
On
Underrange
-0.1
'1111.1111.1111.1111'
0xFFFF
-1
0.0
'0000.0000.0000.0000'
0x0000
0
0x00
Off
Nominal
range
2315.0
'0101.1010.0110.1110'
0x5A6E 23150
2315.1
'0101.1010.0110.1111'
0x5A6F 23151
0x42
On
Overrange
2340.0
'0101.1011.0110.1000'
0x5B68 23400
≥
2340.1
'0111.1111.1111.1111'
0x7FFF 32767
0x60
On
Overflow
1)
Process values below 0 are represented in binary form as the two’s complement.
4.4.3.4 TC Type C – S5-FB250 Format/Celsius
Table 30: TC Type C Setting – S5-FB250 Format/Celsius
Temperature
[°C]
Numeric Value
Status
Byte,
Hex.
Error
LED
Range
Binary
XFÜ
1)
Hex.
Dec.
≤
-26.0
'1000.0000.0000.0 010'
0x8002
-32766
0x50
On
Underflow
-25.0
'1111.1111.0011.1 001'
0xFF39
-199
0x41
On
Underrange
-1.0
'1111.1111.1111.1 001'
0xFFF9
-7
0.0
'0000.0000.0000.0 000'
0x0000
0
0x00
Off
Nominal
range
2315.0
'0100.1000.0101.1 000'
0x4858
18520
2316.0
'0100.1000.0110.0 001'
0x4861
18529
0x42
On
Overrange
2340.0
'0100.1001.0010.0 001'
0x4921
18721
≥
2341.0
'0111.1111.1111.1 010'
0x7FFA
32762
0x60
On
Overflow
1)
Status bits: X= not used, F= error, Ü= overflow