![WAGO 750-464 Скачать руководство пользователя страница 47](http://html1.mh-extra.com/html/wago/750-464/750-464_manual_3197826047.webp)
WAGO-I/O-SYSTEM 750
Commissioning
47
750-464 2/4 AI RTD configurable
Manual
Version 1.0.1
6.2.3
Parameter Sets
For use of the parameter channel, parameter sets are defined and indexed using
parameter addresses (A7 ... A0). Module-specific parameters (parameters 0
through 249) and general system parameters (parameters 250 through 255) are
differentiated.
6.2.3.1
General Parameter Data (System Parameter Range)
The following addresses are defined to access the system parameters of the I/O
modules:
Table 35: System Parameters
Address
Mode Parameter
Description
250 ... 253 R/W
RESERVED
Reserved for expansions
254
R/W
TIMEOUT
This parameter contains the
maximum permissible time in
milliseconds that can elapse for
the transfer of the parameter set.
If TIMEOUT = 0, the
monitoring time is infinite.
255
R
NO_OF_PRMS
Number of words (parameter
data) of the I/O module.
W
SET_DEFAULT_PRMS The I/O module is reset to the
default setting.
Pos : 88 /Serie 750 ( WAGO-I/ O-SYST EM)/I n Betrieb nehmen/ Parametrier en über Paramet er kanal/Paramet er kanaladres sen 750-464 @ 6\ mod_1263292139765_21. doc x @ 47866 @ 4 @ 1
6.2.3.2
I/O Module-Specific Parameter Data
The following addresses are defined for access to the specific parameter data of
the I/O module: