WAGO-I/O-SYSTEM 750
Connect Devices
35
750-464 2/4 AI RTD configurable
Manual
Version 1.0.1
5.2.3
750-464/020-000 (NTC) Version
5.2.3.1
4 x 2-Wire
Important information for 4-channel operation
Please note the special features in the following chapter
Figure 16: Connection example, version 750-464/020-000 (NTC)
5.2.3.2
Special Features
5.2.3.2.1 Influencing a Measuring Circuit Channel through a Quick Change in
Temperature
As a rule, temperatures change relatively slowly. If a channel's applied resistance
changes over a short period of time by a large resistance value (large in relation to
the converted temperature change), then this can influence the other channel
within the measuring circuit.
5.2.3.2.2 Underrange and Wire Break
Depending on the hardware, it is not possible to distinguish between a
(temperature) underrange and a wire break when using the NTC version 750-
464/020-000. In the case of wire break, an underrange is always detected.
Pos : 77 /D okument ation allgemei n/ Glieder ungs elemente/---Seit enwechs el--- @ 3\ mod_1221108045078_0. doc x @ 21810 @ @ 1