Appendix 99
750-458 8AI; TC; Adjust
Manual
Version 1.3.0
Table 56: General module / channel parameters
Parameter
Value
Explanation
Process alarm:
Lower user limit value
undershot
Channel x (x = 0 … 7)
0 (false)
Falling below the lower user limit on the
respective signal channel does not lead to
transmission of a process alarm. The lower user
limit is set in another attribute.
1 (true)
*)
Provided that the channel diagnostics of the
respective signal channel has been activated,
falling below the lower user limit leads to
transmission of a process alarm. No entry in the
diagnostics database of the station proxy is
made. The lower user limit is set in another
attribute.
Lower user limit
−
32768
*)
… 32767
Based on the value range of the input signal, a
lower limit value of the input signal can be
specified that can lead to the abovementioned
event of a process alarm.
Process alarm:
Upper user limit value
exceeded
Channel x (x = 0 … 7)
0 (false)
Exceeding the upper use limit on the respective
signal channel does not lead to transmission of
a process alarm. The upper user limit is set in
another attribute.
1 (true)
*)
Provided that the channel diagnostics of the
respective signal channel has been activated,
exceeding the upper user limit leads to
transmission of a process alarm. No entry in the
diagnostics database of the station proxy is
made. The upper user limit is set in another
attribute.
Upper user limit
−32768
… 32767
*)
Based on the value range of the input signal, an
upper limit value of the input signal can be
specified that can lead to the abovementioned
event of a process alarm.
*)
Default settings
Содержание 750-458
Страница 1: ...Manual 750 458 8AI TC Adjust 8 Channel Analog Input Module Thermocouple Adjustable Version 1 3 0 ...
Страница 63: ...Commissioning 63 750 458 8AI TC Adjust Manual Version 1 3 0 Figure 23 Channel settings Menu Item View ...
Страница 66: ...66 Commissioning 750 458 8AI TC Adjust Manual Version 1 3 0 Figure 24 Scaling Menu Item View ...
Страница 69: ...Commissioning 69 750 458 8AI TC Adjust Manual Version 1 3 0 Figure 25 Calibration Menu Item View ...