38 Process Image
750-458 8AI; TC; Adjust
Manual
Version 1.3.0
Table 24: Process Image Type K, ID3, Two's Complement Representation
Temperature
°C
Numeric value
1)
Status
Byte
Hex.
Error
LED
Binary
Hex.
Dec.
---
'1000.0000.0000.0000'
0x8000
−32768
0x00
OFF
Range violation, cold
junction
< −200.0
'1111.1000.0011.0000'
0xF830
−2000
0x41
ON
Underrange
−200.0
'1111.1000.0011.0000'
0xF830
−2000
0x00
OFF
−100.0
'1111.1100.0001.1000'
0xFC18
−1000
0x00
OFF
0.0
'0000.0000.0000.0000'
0x0000
0
0x00
OFF
100.0
'0000.0011.1110.1000'
0x03E8
1000
0x00
OFF
200.0
'0000.0111.1101.0000'
0x07D0
2000
0x00
OFF
300.0
'0000.1011.1011.1000'
0x0BB8
3000
0x00
OFF
400.0
'0000.1111.1010.0000'
0x0FA0
4000
0x00
OFF
500.0
'0001.0011.1000.1000'
0x1388
5000
0x00
OFF
600.0
'0001.0111.0111.0000'
0x1770
6000
0x00
OFF
700.0
'0001.1011.0101.1000'
0x1B58
7000
0x00
OFF
900.0
'0010.0011.0010.1000'
0x2328
9000
0x00
OFF
1000.0
'0010.0111.0001.0000'
0x2710
10000
0x00
OFF
1200.0
'0010.1110.1110.0000'
0x2EE0
12000
0x00
OFF
1370.0
'0011.0101.1000.0100'
0x3584
13700
0x00
OFF
Overrange
'0011.0101.1000.0100'
0x3584
13700
0x42
ON
> 1370.0
Wire break
'0111.1111.1111.1111'
0x7FFF
32767
0x60
ON
---
1)
Temperature values below 0 °C are represented in two's complement binary.
Содержание 750-458
Страница 1: ...Manual 750 458 8AI TC Adjust 8 Channel Analog Input Module Thermocouple Adjustable Version 1 3 0 ...
Страница 63: ...Commissioning 63 750 458 8AI TC Adjust Manual Version 1 3 0 Figure 23 Channel settings Menu Item View ...
Страница 66: ...66 Commissioning 750 458 8AI TC Adjust Manual Version 1 3 0 Figure 24 Scaling Menu Item View ...
Страница 69: ...Commissioning 69 750 458 8AI TC Adjust Manual Version 1 3 0 Figure 25 Calibration Menu Item View ...