For the voltage measurement with sensor type ±240 mV (ID12), the input range
of −240
mV … +240
mV is mapped to a value range of −24000
… +24000 at a
resolution of 0.01 mV. Voltage values below 0 mV are represented in two's
complement binary. The voltage underranges and overranges refer to
manufacturer range violations.
Table 32: Process Image Voltage Measurement ±240 mV, ID12, Two's Complement
Representation
Voltage
mV
Numeric value
1)
Status
Byte
Hex.
Error
LED
Binary
Hex.
Dec.
< −240.0
'1010.0010.0100.0000'
0xA240
−24000
0x41
ON
Underrange
−240.0
'1010.0010.0100.0000'
0xA240
−24000
0x00
OFF
−210.0
'1010.1101.1111.1000'
0xADF8
−21000
0x00
OFF
−180.0
'1011.1001.1011.0000'
0xB9B0
−18000
0x00
OFF
−150.0
'1100.0101.0110.1000'
0xC568
−15000
0x00
OFF
−120.0
'0010.1110.1110.0000'
0x2EE0
−12000
0x00
OFF
−90.0
'1101.1100.1101.1000'
0xDCD8
−9000
0x00
OFF
−60.0
'1110.1000.1001.0000'
0xE890
−6000
0x00
OFF
−30.0
'1111.0100.0100.1000'
0xF448
−3000
0x00
OFF
0.0
'0000.0000.0000.0000'
0x0000
0
0x00
OFF
30.0
'0000.1011.1011.1000'
0x0BB8
3000
0x00
OFF
60.0
'0001.0111.0111.0000'
0x1770
6000
0x00
OFF
90.0
'0010.0011.0010.1000'
0x2328
9000
0x00
OFF
120.0
'0010.1110.1110.0000'
0x2EE0
12000
0x00
OFF
150.0
'0011.1010.1001.1000'
0x3A98
15000
0x00
OFF
180.0
'0100.0110.0101.0000'
0x4650
18000
0x00
OFF
210.0
'0101.0010.0000.1000'
0x5208
21000
0x00
OFF
240.0
'0101.1101.1100.0000'
0x5DC0
24000
0x00
OFF
Overrange
'0101.1101.1100.0000'
0x5DC0
24000
0x42
ON
> 240.0
Wire break
'0111.1111.1111.1111'
0x7FFF
32767
0x60
ON
---
1)
Temperature values below 0 °C are represented in two's complement binary.
Содержание 750-458
Страница 1: ...Manual 750 458 8AI TC Adjust 8 Channel Analog Input Module Thermocouple Adjustable Version 1 3 0 ...
Страница 63: ...Commissioning 63 750 458 8AI TC Adjust Manual Version 1 3 0 Figure 23 Channel settings Menu Item View ...
Страница 66: ...66 Commissioning 750 458 8AI TC Adjust Manual Version 1 3 0 Figure 24 Scaling Menu Item View ...
Страница 69: ...Commissioning 69 750 458 8AI TC Adjust Manual Version 1 3 0 Figure 25 Calibration Menu Item View ...