Device Description 25
750-458 8AI; TC; Adjust
Manual
Version 1.3.0
3.6.3
Inputs
Table 11: Technical Data, Inputs
Number of inputs
8
Connection types
2-conductor connection, single-ended
Input resistance
≥
10
MΩ
Cold junction compensation
Module-internal based on a cold junction
temperature measurement
Resolution
For temperature measurements
(sensor types ID0 … ID8) 0.1 °C
For voltage measurements
Sensor type ±30 mV (ID9): 0.00125 mV
Sensor type ±60 mV (ID10): 0.0025 mV
Sensor type ±120 mV (ID11): 0.005 mV
Sensor type ±240 mV (ID12): 0.01 mV
Conversion time
Notch filter activated
≤
100 ms (per channel)
Notch filter deactivated
≤
50 ms (per channel)
Conversion method
SigmaDelta
Temperature coefficient
For type K
≤
±0.05 K/K
For voltage measurements
≤
±50 ppm/K of measurement range
Diagnostics
Measurement range underflow
Measurement range overflow
Wire break
Signaling with diagnostics
Status byte
LED