WAGO-I/O-SYSTEM 750
Mounting
27
750-402 4DI 24V DC 3.0ms
Manual
Version 1.1.0
Pos : 71 /All e Seri en (Allgemei ne Module)/Ü berschrif ten f ür alle Serien/Monti eren - D emontieren/M ontier en - Übersc hrift 1 @ 3\ mod_1225446744750_21. doc x @ 24900 @ 11 @ 1
5
Mounting
Pos : 72.1 /Serie 750 (WAGO-I/ O-SYST EM)/M ontieren/D emontieren/M ont agerei henf olge @ 3\ mod_1231770210031_21. doc x @ 25992 @ 2 @ 1
5.1
Mounting Sequence
All system components can be snapped directly on a carrier rail in accordance
with the European standard EN 50022 (DIN 35).
The reliable positioning and connection is made using a tongue and groove
system. Due to the automatic locking, the individual components are securely
seated on the rail after installation.
Starting with the coupler/controller, the I/O modules are mounted adjacent to each
other according to the project design. Errors in the design of the node in terms of
the potential groups (connection via the power contacts) are recognized, as the I/O
modules with power contacts (male contacts) cannot be linked to I/O modules
with fewer power contacts.
Pos : 72.2 /Serie 750 (WAGO-I/ O-SYST EM)/ Wic htige Erläut erungen/ Sicherheits- und sonstig e Hinweis e/ Vorsic ht/ Vorsicht: Verl etz ungsgefahr durc h s charf kantige M ess er kont akt e! @ 6\ mod_1256193279401_21.doc x @ 43414 @ @ 1
Risk of injury due to sharp-edged male contacts!
The male contacts are sharp-edged. Handle the module carefully to prevent injury.
Pos : 72.3 /Serie 750 (WAGO-I/ O-SYST EM)/ Wic htige Erläut erungen/ Sicherheits- und sonstig e Hinweis e/ Achtung/Achtung: Bus kl emmen nur in vorgesehener R eihenfolg e st ec ken! @ 6\ mod_1256194177073_21. doc x @ 43429 @ @ 1
Insert I/O modules only from the proper directions!
All I/O modules feature grooves for power jumper contacts on the right side. For
some I/O modules, the grooves are closed on the top. Therefore, I/O modules
featuring a power jumper contact on the left side cannot be snapped from the top.
This mechanical coding helps to avoid configuration errors, which may destroy
the components. Therefore, insert I/O modules only from the right and from the
top.
Pos : 72.4 /Serie 750 (WAGO-I/ O-SYST EM)/ Wic htige Erläut erungen/ Sicherheits- und sonstig e Hinweis e/Hinweis/Hi nweis: Busabsc hluss nicht vergess en! @ 6\ mod_1256194225557_21. doc x @ 43432 @ @ 1
Don't forget the bus end module!
Always plug a bus end module 750-600 onto the end of the fieldbus node! You
must always use a bus end module at all fieldbus nodes with the WAGO I/O
System 750 fieldbus couplers/controllers to guarantee proper data transfer.