WAGO-I/O-SYSTEM 750 XTR
Device Description 15
750-429/040-001 2DI 60V DC 3ms XTR
Manual
Version 1.2.0
Use a 750-612/040-000 power supply!
For 60 VDC power on the field level, an additional 750-612/040-000 supply
module must be positioned before a terminal block 750-429/040-001 or before
I/O modules 750-429/040-001 arranged in blocks!
The I/O module 750-429/040-001 receives the 60 VDC power supply and the 0 V
potential for the field level from an upstream I/O module via the power jumper
contacts designed as blade contacts and makes the potential available to
subsequent I/O modules via power jumper contacts designed as spring contacts.
Do not exceed maximum values via power contacts!
The maximum current that can flow through the power jumper contacts is 10 A.
The power jumper contacts can be damaged and the permissible operating
temperature can be exceeded by higher current values.
When configuring the system, do not exceed the permissible maximum current
value. If there is a higher power requirement, you must use an additional supply
module to provide the field voltage.
The field voltage and the system voltage are electrically isolated from each other.
With consideration of the power jumper contacts, the individual modules can be
arranged in any combination when configuring the fieldbus node.
An arrangement in groups within the group of potentials is not necessary.
Mixed operation
Mixed operation (standard/XTR modules) within a node is possible when groups
of modules are electrically isolated on the field side (i.e., electrically isolated
power supply).
The I/O module can be operated with all fieldbus couplers/controllers of the
WAGO-I/O-SYSTEM 750 XTR.
Observe the instructions for mixed operation when used in mixed operation
behind standard fieldbus couplers/controllers.