TITANUS
MICRO·SENS
®
Pipe
Design
MS_A_04-en-e
Data: 01/09
4 –
29
4.3.2.3 M-pipe
system
1 Pipe system
TITANUS
MICRO·SENS
P
®
P
TITANUS
®
d
Fig. 4. 12: M-Pipe system, e.g. for equipment protection
Limit values
min. distance TITANUS
P
®
P
– T piece
2 m
max. distance TITANUS
P
®
P
– T piece
20 m
max. branch length
16,5 m
max. overall pipe length per pipe system
Pipe
∅
25 mm plus
pipe
∅
12 mm
50 m
8 x 3 m
max. overall pipe length per pipe system with a ventila-
tor voltage of <10.5 V
Pipe
∅
25 mm plus
pipe
∅
12 mm
40 m
8 x 3 m
max. number of aspiration apertures (n) per pipe system
6 no.
minimum distance between the aspiration apertures (d)
0,1 m
maximum distance between the aspiration apertures (d)
4 m
Aspiration apertures
Number of apertures
3
6
∅
of all aspiration
apertures in mm
TP16F
17
PT
) 5,0
3,6
TP
17
PT
Opening diameter of the aspiration reduction film
Содержание TITANUS
Страница 1: ...Technical Manual Air sampling smoke detection system TITANUS MICRO SENS ...
Страница 2: ......
Страница 4: ......
Страница 10: ...TITANUS MICRO SENS Contents MS_A_Inhalt en e Data 01 09 ...
Страница 14: ...General TITANUS MICRO SENS 0 4 Data 01 09 MS_A_00 en e ...
Страница 44: ...Technical Description TITANUS MICRO SENS 2 24 Data 01 09 MS_A_02 b en e ...
Страница 65: ...TITANUS MICRO SENS Pipe Design MS_A_04 en e Data 01 09 4 15 ...
Страница 124: ...Installation TITANUS MICRO SENS 5 38 Data 01 09 MS_A_05 en e ...
Страница 160: ...Commissioning TITANUS MICRO SENS 7 20 Data 01 09 MS_A_07 en e ...
Страница 172: ......
Страница 178: ......
Страница 189: ......
Страница 190: ......
Страница 191: ......
Страница 192: ......
Страница 193: ......
Страница 194: ......
Страница 195: ......
Страница 196: ......
Страница 198: ......
Страница 204: ...TITANUS MICRO SENS Glossary TMS_A_Glossar e Data 01 09 ...
Страница 206: ......
Страница 208: ......