Installation Pipe System
TITANUS
MICRO·SENS
®
6
– 16
Data: 01/09
MS_A_06-en-e
6.10 Test
adapter
PVC-test adapter
type PA-PVC
Fig. 6.13: Installing the test adapter in the pipe system
The test adapter is stuck into the pipe system immediately next to the
air sampling smoke detection system. The test adapter must always be
closed during normal operation and is only opened for maintenance and
service purposes, to introduce test gas or smoke.
After testing detection in the air sampling smoke detection system and
alarm forwarding, the test adapter must be closed again, otherwise there
will be an air flow fault!