
Pipe Design
TITANUS
MICRO·SENS
®
4 –
20
Data: 01/09
MS_A_04-en-e
Aspiration apertures
Number of apertures
per pipe system
1 2 3 4 5
∅
Aspiration aperture
in mm
TP4F
5
PT
)
A
B
C
D
E
6,8
—
—
—
—
4,6
5,0
—
—
—
4,0
4,2
4,4
—
—
3,4
3,6
3,8
4,0
—
3,0
3,2
3,4
3,6
3,8
Trigger Thresholds I-Pipe system
Trigger threshold
Number of apertures
2
3
4
5
1
blocked aperture
±
30 %
±
20 %
±
15 %
±
10 %
2
blocked apertures
{
TP5F
6
PT
{
±
30 %
±
20 %
3
blocked apertures
{
{
{
{
4
blocked apertures
{
{
{
{
5
blocked apertures
{
{
{
{
… is/are recognised when main air flow set x %
Example
If the blockage of
2
aspiration apertures out of a total
of 5
aspiration
apertures is recognised, then with the help of the diagnosis tool flow
monitoring can be set to
±
20 %
.
For a project planning according to EN 54-20, the air flow monitoring
has to be adjusted to
≤
20 % in either case.
TP
5
PT
Opening diameter of the aspiration reducing film
TP
6
PT
{
not sensible
INSTRUCTION
Содержание TITANUS
Страница 1: ...Technical Manual Air sampling smoke detection system TITANUS MICRO SENS ...
Страница 2: ......
Страница 4: ......
Страница 10: ...TITANUS MICRO SENS Contents MS_A_Inhalt en e Data 01 09 ...
Страница 14: ...General TITANUS MICRO SENS 0 4 Data 01 09 MS_A_00 en e ...
Страница 44: ...Technical Description TITANUS MICRO SENS 2 24 Data 01 09 MS_A_02 b en e ...
Страница 65: ...TITANUS MICRO SENS Pipe Design MS_A_04 en e Data 01 09 4 15 ...
Страница 124: ...Installation TITANUS MICRO SENS 5 38 Data 01 09 MS_A_05 en e ...
Страница 160: ...Commissioning TITANUS MICRO SENS 7 20 Data 01 09 MS_A_07 en e ...
Страница 172: ......
Страница 178: ......
Страница 189: ......
Страница 190: ......
Страница 191: ......
Страница 192: ......
Страница 193: ......
Страница 194: ......
Страница 195: ......
Страница 196: ......
Страница 198: ......
Страница 204: ...TITANUS MICRO SENS Glossary TMS_A_Glossar e Data 01 09 ...
Страница 206: ......
Страница 208: ......