background image

 

 

Subject to modifications, errors excepted · © Wagner Solar GmbH, 2017 · www wagner-solar com 

8

 

 

Wagner Solar GmbH · Sonnenallee 2 · D-35274 Ki49 6421 80 07-0

Figure 12  Insulation of the pipes

mA

 

Insulate pipes: continue pipe insulation into the re-
spective openings in the ratchet closure to avoid heat 
loss at the entering points (fig  12) 

6 Troubleshooting

The flat sealing gaskets may change their density during 
the first few months of operation  This normal settling 
behavior may occasionally lead to dripping  The connec-
tions should therefore re-tightened as required 

7 Maintenance

The cleaning and maintenance of the solar storage tank 
should be carried out every two years together with the 
maintenance of the solar installation  We recommend a 
service contract 

 

Defunct protective anode leads to corrosion of the 
storage 

tank! 

 

      

Over time the built-in protective sacrificial anode is con-
sumed during operation  Check the protective anode af-
ter two years, and afterwards annually    

 

 

- Remove the build in uninsulated sacrificial magne-
sium anode, examine remaining magnesium mass and, 
if necessary, install new anode    

 

 

 

- For sacrificial anodes with insulated installation (MG an-
odes) test the protective current between storage and 
anode (fig  13)  When the value is below 0 3 mA, remove 
and examine the anode and replace if required  

 

- If an impressed current anode is installed, observe the 
related product documentation  A green light signals 
correct function 

 

Check for visible leakage of the fittings  If necessary 
retighten fittings 

 

The proper function of the safety valve regularly has to 
be tested  The blow-off opening must never be closed 
or obstructed 

 

Required cleaning of the storage tank can be carried 
out through the access/cleaning flange  Install new 
gasket when closing!

Regular maintenance must be certified in the Mainte-
nance Protocol by a qualified person in order to render 
the warranty agreement valid 

8 Disassembly and Recycling

At  the  end  of  the  long  operational  lifetime,  the  valu-
able materials  of  the  installation  should  be  recycled  in  
an  environmentally  sound  manner  

Figure 13   To check the factory-installed magnesium protection an-
ode unplug cable and measure current with multimeter

Содержание ECOplus

Страница 1: ...ration 2 3 2 Setting up the Storage 2 3 3 Connecting the Domestic Water Circuit 4 3 4 ConnectingtheSolar andAuxiliary Heating Circuit 5 3 5 Connecting Backup Heater 5 3 6 Installing Temperature Sensors 5 3 7 Install a Impressed Current Anode 6 4 Startup of the System 6 4 1 Acceptance Protocol 6 4 2 System Check 6 4 3 Flushing the Installation 6 4 4 Settings at Boiler and Solar Controllers 6 4 5 Fi...

Страница 2: ...the filled tank Wagner Solar cannot be held liable for damages resulting from improper use 2 Scope of supply The ECOplus solar cylinder is supplied standing upright and screwed onto a pallet The serial no is located on the type label Table 1 Scope of supply fig 2 1 Storage 2 Jacket insulation with hook ratchet closure may be several parts depending on storage type 3 Insulation plug with cap for ac...

Страница 3: ...EN XXX_ECOplus Solar Storage_MA 201026 1WA10603 3 Figure 2 Scope of supply Figure 3 Tilt the storage to insert the inner floor insulation 2 4 8 7 1 6 5 2 3 ...

Страница 4: ...s heated to its maximum tem perature the DHW temperature set at the thermostatic mixing valve will not be exceeded If no thermostatic mixer is fitted maximum vessel temperature must be limited to 65 C at the solar controller Serious danger of scalding Thesolarinstallationmayheatthestoragewatertotem peratures of up to 95 C The installation of a thermostatic mixing valve limits the tap temperatures ...

Страница 5: ...available that can be installed in the 1 socket on the side fig 6 Please observe instructions supplied with the respec tive heating device Laying the mains cable of the electrical heater a heat resistant cable min up to 95 C must be used when laying the cable under the insulation jacket The immersion heater must only be connected to mains after the storage tank is filled If no immersion heater is ...

Страница 6: ...allation Malfunction or damage when storage tank is not ade quately purged In spite of careful production methods some residues of the processes including metal slack may remain inside the pipes the vessel and the heat exchangers These can cause problems during operation of the system and may lead to damage Therefore the system must be flushed before permanent operation starts Also filtering retai...

Страница 7: ...ar cylinder 1 Now set the insulation jacket to the connection side around the connection openings and if in place the immersion heater 2 First lock the ratchet closure into the loosest position and then tighten from the top alternating if the jacket has more than one closure until the jacket tightly fits the storage tank 3 If no immersion heater is fitted insert insulation plug with cap 4 Insert i...

Страница 8: ... in uninsulated sacrificial magne sium anode examine remaining magnesium mass and if necessary install new anode Forsacrificialanodeswithinsulatedinstallation MGan odes test the protective current between storage and anode fig 13 When the value is below 0 3 mA remove and examine the anode and replace if required If an impressed current anode is installed observe the related product documentation A...

Отзывы: