7

5 Place the Insulation

The solar cylinder insulation consists of PU foam with a 
laminated polystyrene cover layer and hook closure (ei-
ther 1 or 2 parts, depending on storage type) 
The higher the ambient temperature, the more flexible 
the PU foam and due to the breakage tendency 
Do not install insulation below 20 °C and allow insulation 
stored at cold temperatures to reach room temperature 
before installing 

Please do not use tools or tightening straps and do not
close the hook closure by force. This could damage the
insulation and diminish its effectiveness.

 

(Fig  11) Place the insulation ring around the bottom of 
the solar cylinder (1) 

 

Now set the insulation jacket to the connection side 
around the connection openings and - if in place - the 
immersion heater (2) 

 

First lock the ratchet closure into the loosest position 
and then tighten from the top (alternating if the jacket 
has more than one closure) until the jacket tightly fits 
the storage tank (3) 

 

If no immersion heater is fitted insert insulation plug 
with cap (4) 

 

Insert insulation plug with cap for access flange (5) 

 

Insert upper circular insulation panel and attach lid (6) 

Figure 9  Filling and venting the storage

Figure 10  Monitor pipe connections for leak tightness and opera-
tional pressure

Figure 11  Place the insulation

bar

1

2

4

6

3

5

 

Heat the content of the storage cylinder, for example 
by switching on the boiler, and keep checking the pres-
sure  Before reaching maximum operational pressure, 
the safety valve must come into operation 

17

9

Содержание ECOplus

Страница 1: ...ration 2 3 2 Setting up the Storage 2 3 3 Connecting the Domestic Water Circuit 4 3 4 ConnectingtheSolar andAuxiliary Heating Circuit 5 3 5 Connecting Backup Heater 5 3 6 Installing Temperature Sensors 5 3 7 Install a Impressed Current Anode 6 4 Startup of the System 6 4 1 Acceptance Protocol 6 4 2 System Check 6 4 3 Flushing the Installation 6 4 4 Settings at Boiler and Solar Controllers 6 4 5 Fi...

Страница 2: ...the filled tank Wagner Solar cannot be held liable for damages resulting from improper use 2 Scope of supply The ECOplus solar cylinder is supplied standing upright and screwed onto a pallet The serial no is located on the type label Table 1 Scope of supply fig 2 1 Storage 2 Jacket insulation with hook ratchet closure may be several parts depending on storage type 3 Insulation plug with cap for ac...

Страница 3: ...EN XXX_ECOplus Solar Storage_MA 201026 1WA10603 3 Figure 2 Scope of supply Figure 3 Tilt the storage to insert the inner floor insulation 2 4 8 7 1 6 5 2 3 ...

Страница 4: ...s heated to its maximum tem perature the DHW temperature set at the thermostatic mixing valve will not be exceeded If no thermostatic mixer is fitted maximum vessel temperature must be limited to 65 C at the solar controller Serious danger of scalding Thesolarinstallationmayheatthestoragewatertotem peratures of up to 95 C The installation of a thermostatic mixing valve limits the tap temperatures ...

Страница 5: ...available that can be installed in the 1 socket on the side fig 6 Please observe instructions supplied with the respec tive heating device Laying the mains cable of the electrical heater a heat resistant cable min up to 95 C must be used when laying the cable under the insulation jacket The immersion heater must only be connected to mains after the storage tank is filled If no immersion heater is ...

Страница 6: ...allation Malfunction or damage when storage tank is not ade quately purged In spite of careful production methods some residues of the processes including metal slack may remain inside the pipes the vessel and the heat exchangers These can cause problems during operation of the system and may lead to damage Therefore the system must be flushed before permanent operation starts Also filtering retai...

Страница 7: ...ar cylinder 1 Now set the insulation jacket to the connection side around the connection openings and if in place the immersion heater 2 First lock the ratchet closure into the loosest position and then tighten from the top alternating if the jacket has more than one closure until the jacket tightly fits the storage tank 3 If no immersion heater is fitted insert insulation plug with cap 4 Insert i...

Страница 8: ... in uninsulated sacrificial magne sium anode examine remaining magnesium mass and if necessary install new anode Forsacrificialanodeswithinsulatedinstallation MGan odes test the protective current between storage and anode fig 13 When the value is below 0 3 mA remove and examine the anode and replace if required If an impressed current anode is installed observe the related product documentation A...

Отзывы: