3.3 Mounting to Cylinder
The adjustable mounting kits can be used with all Wagner
solar cylinders with 1¼" flat tightening connections, if the
vertical distance of these is between 400 and 640 mm.
In order to prevent later obstructions of the pipe work in
the area of the cylinder it is necessary to make proper lay-
out plans before commencing.
●
Connect pipes to cylinder using supplied gaskets.
●
Adjust the height adjustment until both pipes are reach-
ing the same level and have a distance of 125mm.
Tighten adjustment nut.
●
Trim off the insulation of the adjustable pipe and place
pump station on top.
●
Level the unit and affix to the cylinder.
●
Connect remaining pipe work.
In order to prevent forces to the cylinder fixing because of
pull from pipe work, pipe fixtures should be used at a near
wall or at the ceiling.
The expansion vessel must not be hung from the pump sta-
tion. Apply wall or floor mounting, depending on type of
vessel.
●
Always ensure proper clamping when tightening 32, 41
and 46 mm nuts in order to prevent loosening of other
joints or damage to the unit.
Figure 7 The adjustable cylinder mounting kit consisting of:
Adjustable return pipe fitted with filler and drain valve, including insula-
tion and fittings: 1¼" nut and 22 mm sleeve for compression joint.
Flow pipe including insulation and fittings: 1¼" nut and 22 mm sleeve
for compression joint.