3.1 Installation Preparations

The entire layout of flow and return pipes should be
clear before mounting the CIRCO 5 solar circulation unit
(125 mm centres)!
In this context please also observe the operation instruc-
tions "Commissioning the System"

If the solar system is installed for heating or if vacuum
tubes are used you must pay attention to the technical
documentation “Heat Protection”.

These tools are required for the installation of the
CIRCO 5 solar circulation unit: Power drill, masonry bits,
pipe wrench, stilton etc. (figure 5).

3.2 Wall Mounting

Use spirit level to place the wall mounting bracket

(1)

,

see figure 4, into the correct position, mark the three
holes, drill and fix with plugs and screws supplied.

Place the two pieces of assembly

(2+6)

into the correct

holders of the wall mounting bracket and affix with the
two spring clips

(3)

.

Place the two halves of the back insulation

(4)

with the

recesses over the wall mounting bracket and push to-
gether.

Connect the safety group

(5)

with the included ¾" gas-

ket to the free exit of the return unit

(6)

using an open

wrench SW30.
Make sure of proper clamping during the tightening of
the compression fittings to prevent damage or loosen-
ing of other parts of the assembly.

Use the included wall anchors and screws to connect
wall-mount

(7)

for the expansion vessel

(8)

to the right of

the safety group. Observe length of the ¾" corrugated
tube

(9)

. There are special wall mounting kits for 35 litre

and 50 litre vessels.

Connect the flexible hose with the expansion vessel and
the pump station using supplied ¾ “ gaskets. It is recom-
mended to fit in a special cap check valve between flexi-
ble hose and vessel.

Connect exhaust pipe

(10)

to the safety unit and put

empty container in place to collect any spills from the
pipe.

The connections to the solar circuit

(11)

(distance of

pipes see figure 3) are made by compression fittings 18
or 22 mm (figure 6) .
Cut, burr pipes and push into fittings as far as possible,
then tighten nuts. Using the 18 mm compression fitting a
cracking sound will be heard, which is a sign of proper
tightening. Continue until fully tight.
Do not solder 18 mm compression fitting.
Here too, special care must be taken to ensure proper
clamping to prevent damage or loosening of other parts
of the assembly.

Rinse solar pump station and solar circuit and check for
leaks. For this procedure a filler valve is fitted to the
safety unit

(5)

and the flow meter below the pump.

Install electrical wiring, switching and sensor circuits

(12)

. Fix cables with cable ties to the prepared sections

(notches and long holes) to the wall mounting bracket
and ensure that there are no forces on the connectors of
the control unit and that there is no contact with hot pip-
ing. If required feeding holes can be enlarged with a
sharp knife.
Always disconnect mains when working with electrical
equipment!

Remove frame

(13)

from the pump station in order to in-

stall the SUNGO control.

Open SUNGO control

(14)

and affix with the four screws

(15)

supplied to the wall mounting bracket. You will find

all required installation and operating instructions in the
manuals for SUNGO S, SUNGO SL and SUNGO SXL.

Put front insulation

(16)

into place.

compression fitting

for 22 mm

compression fitting

for 18 mm

snapping

point

Figure 5 Tools required for the installation of the CIRCO 5 solar circula-
tion unit

Figure 6 Compression fittings 18 and 22mm

Содержание CIRCO 5

Страница 1: ...lers Controlled heat flow by two temperature resistant non return ball valves Safe deaeration by integrated air venting pipe Variable Installation wall mounting or fitted directly to the storage cylinder the reliable pump station for efficient circulation of the heating fluid in combination with SUNGO controls CIRCO 5 Solar Circulation Unit Function Control through flow meter and thermometers Figu...

Страница 2: ...d the appli cation of vacuum tube collectors do require special means of overheating protection like the installation of an auxiliary vessel or alternative positioning of the safety components The CIRCO 5 solar circulation unit can be mounted to a wall or directly to the storage cylinder The CIRCO 5 solar circulation unit must not be mounted outside Norms and guidelines EC conformity declaration T...

Страница 3: ... the entire system collector area and heightabove vessel distance vessel to upper edge of collectors Dimensioning scenario system exposed to full sun light but inactive These values are only valid up to about 0 5 litres per m collector volume 0 0 5 1 5 2 0 0 0 1 0 2 0 3 0 m h 3 m s H m econom y 1 0 6 7 5 4 2 1 3 v m axim um Figure 2 Pump characteristics curves CIRCO 5 solar circulation unit Order ...

Страница 4: ... numbering fits to numbers in brackets at description of assembling steps items with No 7 8 9 10 12 and 14 are not part of the circulation unit ball valve with integrated thermometer and non return valve air release pipe safety valve compression fitting compression fitting mano meter filler and drain valve circulation pump flow meter with filler and drain valve ...

Страница 5: ...com mended to fit in a special cap check valve between flexi ble hose and vessel Connect exhaust pipe 10 to the safety unit and put empty container in place to collect any spills from the pipe The connections to the solar circuit 11 distance of pipes see figure 3 are made by compression fittings 18 or 22 mm figure 6 Cut burr pipes and push into fittings as far as possible then tighten nuts Using t...

Страница 6: ...ylinder Connect remaining pipe work In order to prevent forces to the cylinder fixing because of pull from pipe work pipe fixtures should be used at a near wall or at the ceiling The expansion vessel must not be hung from the pump sta tion Apply wall or floor mounting depending on type of vessel Always ensure proper clamping when tightening 32 41 and 46 mm nuts in order to prevent loosening of oth...

Страница 7: ...low Stoppers When the circulation pumps are turned of unwanted heat distribution in the solar circuit is prevented by non return ball valves They only open into the flow direction and by pump pressure The ball valve handles can be used to turn them off During operation Filling the system Emptying the system Flow on Ball valve handle vertical Non return valve in operation Flow off Ball valve handle...

Страница 8: ...sion vessel kit Expansion vessel for the CIRCO 5 solar circulation unit operating pressure max 10 bar stainless steel connection hose connection female with gasket 12 l volume incl wall mounting bracket pre pressurised 1 5 bar 18 l volume incl wall mounting bracket pre pressurised 1 5 bar 24 l volume incl wall mounting bracket pre pressurised 1 5 bar 35 l volume with brackets for wall and floor fi...

Отзывы: