EN
Operation
AirConServiceCenter
86
I
✓
After flushing is completed, the AirConServiceCenter goes into
standby mode.
19. If necessary, remove the adapter from the flushing circuit and recon-
nect all the components to the refrigerant circuit.
Fit the connections of the AirConServiceCenter to the vehicle
air conditioning system and open them.
20. In standby mode, use the cursor keys
or
to select
“Free selection
”:
21. Press
ENTER
to confirm.
22. If necessary, enter the desired data with the keypad (
7
) and press
ENTER
to confirm.
If you do not want to enter any data here, press
ENTER
to advance
to the next program step.
23. Deselect
“Rec/Recycling phase ?
” with
No
(the chosen setting
flashes) and press
ENTER
to confirm.
24. Select
“Vacuum phase ?
” (the chosen setting flashes) and press
ENTER
to confirm.
25. If necessary, enter the desired data with the keypad (
7
) and press
ENTER
to confirm.
If you do not want to enter any data here, press
ENTER
to advance
to the next program step.
26. Select
“Filling phase
” (the chosen setting flashes) and press
ENTER
to confirm.
27. Enter the refrigerant filling quantity (note the oil filling quantity of
the compressor).
28. Then follow the instructions in the display (
6
):
Select the setting (which then flashes) and press
ENTER
to confirm.
29. Select
“Process start
” with
ENTER
.
✓
After the filling is complete, you are prompted to disconnect the hoses
of the AirConServiceCenter from the vehicle air conditioning system.
NOTE
If the refrigerant has been contaminated (analysis only possible with
ASC2000RPA), abort the air conditioning service and use the refrig-
erant draining station, WAECO item number 8885200059, to drain
the air conditioning system.
ASC2000RPA only:
if applicable, the message “NCG evacuation”
appears in the display (
6
) once the recycling phase has been com-
pleted. Non-condensable gases (such as air or oxygen) are auto-
matically released into the surrounding air.
Short selection
Free selection
Other selections
ENTER-OK
Содержание AirConServiceCenter ASC1000
Страница 2: ......
Страница 216: ...RU AirConServiceCenter 216 2 2 1 AirConServiceCenter AirConServiceCenters AirConServiceCenter AirConServiceCenter 405 C...
Страница 218: ...RU AirConServiceCenter 218 2 3 405 C R 134a...
Страница 219: ...RU 219 AirConServiceCenter 2 4 TRG 402 AirConServiceCenter...
Страница 220: ...RU AirConServiceCenter 220 2 5 AirConServiceCenter 230 50 2 6...
Страница 224: ...RU AirConServiceCenter AirConServiceCenter 224 10 11 12 13 14 15 16 5 2 17 18 19 20 21 ASC2000RPA 22 21 17 18 19 20 22...
Страница 229: ...RU 229 AirConServiceCenter 6 6 232 1 20 17 18 19 2 20 3 ASC2000 ASC2000RPA ASC3000 230 20 17 18 19...
Страница 233: ...RU 233 AirConServiceCenter 6 10 ASC2000RPA I 1 12 2 8 3 12 AirConServiceCenter 8...
Страница 238: ...RU AirConServiceCenter 238 I 7 2 2 1 STOP Enter user code Wrong code Max Mustermann...
Страница 251: ...RU 251 AirConServiceCenter 8 Process start ENTER 9 D 10 E 11 15 D D E...
Страница 252: ...RU AirConServiceCenter 252 8 3 ASC2000RPA I 1 21 2 3 4 8 4 AirConServiceCenter 21 WAECO 4440600076 21...
Страница 254: ...RU AirConServiceCenter 254 8 5 1 10 2 D E 3 AirConServiceCenter I 4 G 5 J AirConServiceCenter D D E E H J G I...
Страница 259: ...RU 259 AirConServiceCenter 9 9 1 A 9 2 9 3 AirConServiceCenter WAECO...
Страница 262: ...RU AirConServiceCenter 262 Error 01 Error 02 Error 03 Error 04 Error 05 4 Error 07 14 Error 08 Error 09 Error 10...
Страница 263: ...RU 263 AirConServiceCenter Error 11 Error 12 10 C Error 60 Error 61...
Страница 267: ...RU 267 AirConServiceCenter...