Operation
GV 2500A
wc_tx000269gb.fm
20
3.7
Control Panel
See Graphic: wc_gr001251
The circuit breaker protects the generator from severe overloads or
short circuits. If the circuit breaker opens, turn the engine off
immediately and determine the cause before restarting. Check the
appliances and tools attached to the generator for defects and make
sure their power requirements do not exceed the power rating of the
generator or the current limit of the receptacles.
When the circuit breaker opens, the button will pop out. To reset circuit
breaker, push button in.
Note: Enlargements of receptacles show protective covers removed
for identification purposes only. Never remove protective covers.
Ref.
Description
Ref.
Description
a
Main circuit breaker - 10 amps
b1
Schuko IP44 (CEE 7) receptacle
230V, 16 Amp
b2
CEE receptacle IP44 2P+E
230V, 16 Amp
b3
Swiss IP44 receptacle
230V, 16 Amp
b4
French IP44 receptacle
230V, 16 Amp
wc_gr001251
a
b1
b2
b3
b4