15 - URDR001A - User manual
7.8
Heater Break Alarm on CT (Current Transformer)
This function allows to measure load current to manage an alarm during a malfunctioning with power
in short circuit, always open or partial break of the charge. To enable this function set
50 Hz
or
60 Hz
on
par. 287
ct F.
and the value of the connected transfomer, on par. 288
ct v.
.
• Select on par. 290
H.b.a.t.
the Heater Break Alarm intervention threshold in Ampere.
• Select on par. 291
ocu.t.
the intervention threshold in Ampere to control the overcurrent.
• Select on par. 292
H.b.a.d.
the delay time in seconds for the Heater Break Alarm intervention.
• It is possible to associate an alarm, selecting
H.b.a.
on par. 123
aL.1.F.
on par. 141
aL.2.F.
or par. 159
aL.3.F.
or par. 177
aL.4.F.
or par. 195
aL.5.F.
.
It is possible to visualize on display 2 the average current, selecting
AMPEr.
on par. 278
vi.d.2
.
Selecting 0 on par. 290
H.b.A.t.
it is possible to visualize the current consumption without generating
an Heater Break Alarm.
7.9
Dual Action (Heating-Cooling)
DRR244 is suitable also for systems requiring a combined heating-cooling action.
The command output has to be configured as PID for Heating (Par. 38
ac.t.1
=
Heat
and
P.b. 1
greater
than 0), and one of the alarms (
AL.1.F.
,
AL.2.f.
,
AL.3.f.
,
AL.4.f.
,
AL.5.f.
) has to be configured as
cooL.
The command output must be connected to the actuator responsible for heating, while the alarm will
control cooling action.
Parameters to be configured for the heating PID are:
ac.t.1
=
Heat
Command output action type (Heating);
P.b. 1
: Heating proportional band;
i.t. 1
: Integral time of heating and cooling;
d.t. 1
: Derivative time of heating and cooling;
c.t. 1
: Heating time cycle.
Parameters to be configured for the cooling PID related to regulation loop 1 and alarm 1 are:
AL.1.F.
=
cooL.
Alarm 1 selection (Cooling);
p.b.m.1
: Proportional band multiplier;
o.d.b.1
: Overlapping / Dead band;
c.c.t.1
: Cooling time cycle.
Par.
p.b.m.1
(that ranges from 1.00 to 5.00) determines the proportional band of
cooling action basing on the formula:
Proportional band for cooling action
=
p.b. 1
x
p.b.m.1.
This gives a proportional band for cooling which will be the same as heating band if
p.b.m.1
= 1.00, or 5
times greater if
p.b.m.1
= 5.00.
Integral and derivative time are the same for both actions
.
Par.
o.d.b.1
determines the percentage overlapping between the two actions. For systems in which
the heating output and cooling output must never be simultaneously active a Dead Band (
o.d.b.1
≤ 0),
must be configured, vice versa you can configure an overlapping (
o.d.b.1
> 0).
The following figure shows an example of dual action PID (heating-cooling) with
i.t. 1
= 0 e
d.t. 1
= 0.
1
ACTIVE
ACTIVE
SPV
PV
x
=
COOL
x
=
COOL
x
=
COOL
<
0
=
0
>
0
(
HEAT
)
(
HEAT
)
(
HEAT
)
COMMAND OUTPUT (
HEAT
)
ALARM OUTPUT (
COOL
)
COMMAND OUTPUT (
HEAT
)
ALARM OUTPUT (
COOL
)
COMMAND OUTPUT (
HEAT
)
ALARM OUTPUT (
COOL
)
SPV
PV
ACTIVE
ACTIVE
SPV
PV
ACTIVE
ACTIVE
Содержание URDR001A
Страница 1: ...Controller User manual URDR001A ...
Страница 2: ...2 URDR001A User manual ...