35 - URDR001A - User manual
130
A.1.u.L.
Alarm 1 Upper Limit
Upper limit selectable for the alarm 1 setpoint
-9999..+30000 [digit
1 p. 54
] (degrees for temp. sensors).
Default
1750.
131
a.1.re.
Alarm 1 Reset
Alarm 1 contact reset type (always automatic if AL.1.F. = c. Aux).
A. rEs.
Automatic reset (
Default
)
M. rEs.
Manual reset (manual reset by keyboard or by digital input)
M.rEs.S.
Stored manual reset (keeps the output status also after a power failure)
A. rEs.t.
Automatic reset with timed activation. The alarm remains active for the time set on the
parameter 134
a.1.de.
, even if the conditions generating it are missing. To be able to act
again, the alarm conditions must disappear.
132
A.1.S.e.
Alarm 1 State Error
Alarm 1 output status in case of error.
open
Open contact.
Default
CLose
Closed contact.
133
A.1.Ld.
Alarm 1 Led
Defines the status of the led
A1
in correspondence of the relevant output
o.c.
ON with open contact or DO switched off.
c.c.
ON with closed contact or DO switched on. (
Default
)
134
a.1.de.
Alarm 1 Delay
Alarm 1 Delay.
-60:00..60:00 mm:ss (hh:mm if
AL.1.F.
=
c. aux
).
Default
: 00:00.
Negative value: delay when exit alarm status.
Positive value: delay when enter alarm status.
135
A.1.S.p.
Alarm 1 Setpoint Protection
Allows or not to change the alarm 1 setpoint
FrEE
Editable by the user (
Default
)
Lock
Protected
HidE
Protected and not visualized
136
A.1.Lb.
Alarm 1 Label
Selects the message displayed in case of alarm 1 intervention.
disab.
Disabled. (
Default)
0.
lb. 01
Message 1 (see table on paragraph
13.1
)
..
lb. 16
Message 16 (see table on paragraph
13.1
)
user.l.
Custom message (modifiable by the user through the App or via modbus)
137÷140
Reserved Parameters - Group G
Reserved parameters - Group G