23 - URDR001A - User manual
Modbus
address
Description
Read
Write
Reset
value
1354
Alarm 4 lower setpoint if Par. 177
AL.4.F.
=
A.band
, with decimal point
selection
R/W EEPROM
1355
Alarm 5 lower setpoint if Par. 195
AL.5.F.
=
A.band
, with decimal point
selection
R/W EEPROM
2001
Parameter 1
R/W EEPROM
2002
Parameter 2
R/W EEPROM
...
Parameter ...
R/W EEPROM
2366
Parameter 366
R/W EEPROM
8.1
Serial compatibility with URDR0001
In existing plants where it is necessary to replace an URDR0001 it is possible to install a new URDR001A
enabling the Modbus register’s compatibility.
To enable the Modbus register’s compatibility with the URDR0001, simply enter the password 0243.
To return again to the URDR001A Modbus mapping, enter the password 0244.
The new register map is the following:
Modbus
address
Description of compatibility registers
R/W
Reset
value
0
Device type
RO
EEPROM
1
Software version
RO
EEPROM
5
Slave address
RO
EEPROM
6
Boot version
RO
EEPROM
50
Automatic addressing
WO
-
51
System code comparison
WO
-
500
Loading default values (write 9999)
R/W 0
510
Setpoints storing time in eeprom (0-60 s)
R/W 10
999
Process subjected to the visualization filter
RO
-
1000
Process (degrees.tenths for temperature sensors; digits for linear sensors) RO
-
1001
Setpoint 1
R/W EEPROM
1002
Setpoint 2
R/W EEPROM
1003
Setpoint 3
R/W EEPROM
1004
Setpoint 4
R/W EEPROM
1005
Alarm 1
R/W EEPROM
1006
Alarm 2
R/W EEPROM
1007
Alarm 3
R/W EEPROM
1008
Setpoint gradient
RO
EEPROM
1009
Relay status (0 = Off, 1 = On):
Bit 0 = Relay Q1
Bit 1 = Relay Q2
Bit 2 = Reserved
Bit 3 = SSR
RO
0
1010
Heating output percentage (0-10000)
R/W 0
1011
Cooling output percentage (0-10000)
RO
0
1012
Alarms status (0 = None, 1 = Active)
Bit 0 = Alarm 1
Bit 1 = Alarm 2
RO
0
1013
Manual reset: write 0 to reset all alarms.
In reading (0 = Not resettable, 1 = Resettable)
Bit 0 = Alarm 1
Bit 1 = Alarm 2
R/W 0