5.6 Output signal adaptation
5.6.1 SIGNAL:U (Type and polarity of the output signal)
Command
Parameter
Unit
Group
SIGNAL:U X
x= U+-10|I4-12-20|
U-+10|I20-12-4|
V|mA
STD
This command defines the type of the output signal (current / voltage) and its polarity.
You can also choose between differential and unipolar output types.
Differential voltage for +/- 100%
o
+-10V
o
-+10V
Between PIN 15 and 16.
Single ended current with zero point at 12mA for +/- 100%
o
4-12-20mA
o
20-12-4mA
Between PIN 15 and 12.
An output current of < 4 mA indicates an error and the module is disabled. The current input of the
proportional valves should be monitored by the valve. The valve have to be deactivated in case of
< 4 mA input signal. Otherwise the EOUT command can be used to get a defined output signal.