5.3.4 PIN:5 (F
unction
of Pin 5)
Command
Parameters
Unit
Group
PIN:5
x
x= RAMP|PSET
RAMP
EXP
With this command, the mode of action of the control pins can be set to terminal 15.
Command RAMP: With input signal on terminal 15, the ramps are activated. Without input signal, the ramps
are disabled.
Command PSET:
It can be switched to pin 5 between two parameter sets. It can also be switched between
two ramp parameters.
5.3.5 EOUT (Output signal if not ready)
Command
Parameters
Unit
Group
EOUT X
x= -10000… 10000 0,01 %
EXP
Output value in case of a detected error or a deactive ENABLE input. A value (degree of valve opening) for
use in the event of a sensor error (or the module is disabled) can be defined here. This function can be used if,
for example, the drive is to move to one of the two end positions (at the specified speed) in case of a sensor
error.
|EOUT| = 0
The output is switched off in the event of an error. This is normal behavior.
CAUTION!
If the output signal is 4… 20 mA, the output is switched off when
|EOUT| = 0
. If a null
value = 4 mA is to be output in the event of an error, EOUT must be set to 1
2
.
The output value defined here is stored permanently (independently of the parameter set). The
effects should be analyzed by the user for each application from the point of view of safety.
2
This is necessary if using valves without error detection for signals lower than 4 mA. If the valve has an error detection it
goes into a defined position after switching of the output.