5.2.30
OFFSET1 / OFFSET2 (Zero correction)
Command
Parameters
Unit
Group
OFFSET1
X
OFFSET2
X
x= -4000… 4000
0,01%
STD
This parameter is entered in 0.01% units.
The offset value is added to the control element signal at the output. Control element (valve) zero offsets
can be compensated with this parameter.
5.2.31
INPOS:S1 / INPOS:S2 (In position window)
Command
Parameters
Unit
Group
INPOS:S1 X
INPOS:S2 X
x= 2… 10000
µm
STD
This parameter is entered in µm.
The INPOS:S command defines a monitoring window in which the INPOS:S message is displayed. The
monitoring window is placed centrally on the required position value. The actual position value within this
window is signalled by the INPOS:S message at the status output (see signal description PROFIBUS).
The positioning process is not influenced by this message. The control remains active.
5.2.32
INPOS:D1 / INPOS:D2 (following error window)
Command
Parameters
Unit
Group
INPOS:D1 X
INPOS:D2 X
x= 2… 100000
µm
STD
This parameter is entered in µm.
The INPOS:D command defines a monitoring window in which the INPOS:D message is displayed. The
monitoring window is placed centrally on the required position value. The actual position value within this
window is signalled by the INPOS message at the status output (see signal description PROFIBUS). The
positioning process is not influenced by this message. The control remains active.
In NC Mode this message is used to monitor the following error (depending on the parameterisation).