INSTALLATION

1.    Remove packing material from switch body-cap and remove tape from magnet

keeper. Adjust vane length if necessary on multi-layer vanes only (see flow

rate charts on next page). Install switch in thredolet previously welded to  line.

In some cases, it may be necessary to install the switch in a flange or tee (see

installation drawings on next page). Note: extreme care must be exercised in

welding the fitting to the line so that it is plumb and level.

       ADJUSTMENT OF MULTI-LAYER VANE

       Remove only those layers which are too long. Leave the smaller layers to 

       reinforce the vane. The longest vane fits 6˝ (150 mm) or larger pipe, the 

       second longest vane fits 4˝ (100mm) pipe, etc. Actuation-Deactuation rates 

       are shown in the charts on the next page. To remove vane layers, proceed as

       follows: 

       a. Remove the two screws and lockwashers holding the layers together. Do

not lose these special corrosion resistant type 316 stainless steel screws and

lockwashers.

       b. Remove the unwanted layers.

       c. Resecure the vane with the original two screws and lockwashers.

       d. With a hammer, lightly peen the ends of the screws so that they can't back

out.

       e. If you lose the screws or lockwashers, don't replace with other parts which

may corrode and break. That will void the warrantee and might cause severe

damage to equipment located downstream of the switch.

       

       

Note:

Custom  vane  units  have  been  calibrated  at  factory  to  meet

requirements. Do not change.

2.    The arrow on the side of the switch must point in the direction of flow.

3.    Wiring: UL and CSA units only: thread connecting wires through conduit and

connect. Wire in accordance with local electrical codes.

       Black - Common

       Blue - N.O.

       Red - N.C.

       

       

Note:

Double pole, double throw switches have dual black, blue and red 

       leads. These are connected in the same manner as single pole, double throw 

       switches, as described above.

       ATEX and IECEx Installation Instructions:

       Cable Connection

       The cable entry device shall be certified in type of explosion protection 

       flameproof enclosure “d”, suitable for conditions of use and correctly installed. 

       Cable entry may exceed 70°C. Conductors and cable gland rated ≥95°C shall 

       be used.

       Conduit Connection

       An Ex d certified sealing device such as a conduit seal with setting compound 

       shall be provided immediately to the entrance of the  valve housing. Cable 

       entry may exceed 70°C. Conductors and cable gland rated ≥95°C shall be 

       used.

       

       

Note:

The switch is deactivated and contacts are in normal condition when 

       there is no flow in the line.

4.    Make sure conduit or cable are properly sealed. Electrical components must

be kept free of moisture, including condensation, at all times. 

CAUTION:

To

prevent  ignition  of  hazardous  atmosphere,  disconnect  the  device  from  the

supply circuit before opening. Keep assembly tightly closed when in operation.

       

Note:

ATEX and IECEX units only: The temperature class is determined by

the maximum ambient and or process temperature. Units are intended to be

used  in  ambient  of  -20°C≤Tamb≤73°C.  Units  may  be  used  in  process

temperatures  up  to  133°C  providing  the  enclosure  and  switch  body

temperature  do  not  exceed  73°C.  The  standard  Temperature  Class  is  T6

Process Temp ≤73°C.

F G

E

C

D

1

2

3

4

5

6

7

8

9

10

8

9

10

4

6

7

3

STANDARD V4

CENELEC V4

PROCESS CONNECTION
1-1/2 MALE NPT

3-11/32
[84.93]

2-23/32
[69.06]

1-5/8 [41.28]
CLEARANCE FOR
COVER REMOVAL

1
[25.40]

A

B

Ref #

1

2

3

4

5

6

7

8

9

10

Standard V4

N/A

N/A

Explosion-proof housing with 3/4˝

female NPT conduit connection.

16 AWG, 6˝ (152 mm) long.

Internal

Magnet arm and switch assembly. 

Switch body of SAE 72 Brass or

316 SS.

Five layer vane, 316 Stainless

Steel, Designed for 1/2˝ to 8˝

pipes. Usable in larger pipe sizes.

Magnet keeper of 430 Stainless

Steel.

Vane block of 316 Stainless Steel.

ATEX/IECEx unit

Cover lock.

External ground.

Explosion-proof housing with 3/4˝

female NPT conduit connection.

Terminal Block

Internal ground.

Magnet arm and switch assembly.

Switch body of SAE 72 Brass or

316 Stainless Steel.

Five layer vane, 316 Stainless

Steel, Designed for 1/2˝ to 8˝ pipes.

Usable in larger pipe sizes.

Magnet keeper of 430 Stainless

Steel.

Vane block of 316 Stainless Steel.

Dim

A

B

C

D

E

F

G

V4 in(mm)

8-3/16 (207.96)

6 (152.40)

4-11/16 (119.06)

1 (25.40)

1-5/16 (33.34)

7/8 (22.23)

11/16 (17.46)

V4-2 in(mm)

8 (203.20)

6-3/4 (171.45)

3-15/16 (100.01)

1-3/4 (44.45)

9/16 (14.30)

11/16 (17.63)

1/2 (12.70)

ATEX/IECEx unit

5. For units supplied with both internal ground and external bonding terminals, the

ground screw inside the housing must be used to ground the control. The external

bonding  screw  is  for  supplementary  bonding  when  allowed  or  required  by  local

code. When external bonding conductor is required, conductor must be wrapped a

minimum of 180° about the external bonding screw. See below.

FRONT VIEW DETAIL

SIDE VIEW DETAIL

CLAMP

SCREW

LOCKWASHER

CONDUCTOR

Standard V4

TERMINAL CONNECTIONS SPDT

TERMINAL CONNECTIONS DPDT

Содержание FlotecT V4 series

Страница 1: ...d processing plants around the world A unique magnetically actuated switching design gives superior performance There are no bellows springs or seals to fail Instead a free swinging vane attracts a ma...

Страница 2: ...specifications for rating NACE Heat Treated Body Neoprene Boot No Electrical Housing Socket Weld Connection Terminal Block Wire Connections Time Delay Relay On flow decrease Time Delay Relay On flow i...

Страница 3: ...ay exceed 70 C Conductors and cable gland rated 95 C shall be used Note The switch is deactivated and contacts are in normal condition when there is no flow in the line 4 Make sure conduit or cable ar...

Страница 4: ...1 2 3 4 1 2 3 4 5 1 5 PIPE 32 17 15 8 2 PIPE 65 32 30 20 23 13 10 6 3 PIPE 210 105 100 50 120 70 60 30 60 48 30 20 4 PIPE 400 200 190 90 195 140 90 70 135 100 60 50 65 50 30 20 6 PIPE 950 475 450 220...

Страница 5: ...n innerhalb des soliden metallischen K rpers der wiederum einen Mikroschalter ausl st HAUPTMERKMALE Leckagedichter K rper Eine Auswahl an kundenspezi schen Paddeln Modell V4 ist einstellbar vom Kunden...

Страница 6: ...muss auch die anderen als Edelstahl haben Monel ATEX 1 1 2 47 8 mm Buchse BSPT Prozessanschluss M25 x 1 5 Leerrohranschluss IECEx Epoxy beschichtetes Gehaeuse Full Swing Vane Flow Test Report Hochdru...

Страница 7: ...leingangstemperatur kann ber 70 C betragen Es sind Anschl sse und Kabelverschraubungen f r 95 C zu verwenden Bemerkung Der W chter ist deaktiviert und die Kontakte sind in normaler Schaltung wenn sich...

Страница 8: ...1 2 3 4 1 2 3 4 5 1 5 PIPE 32 17 15 8 2 PIPE 65 32 30 20 23 13 10 6 3 PIPE 210 105 100 50 120 70 60 30 60 48 30 20 4 PIPE 400 200 190 90 195 140 90 70 135 100 60 50 65 50 30 20 6 PIPE 950 475 450 220...

Страница 9: ...t provoquer des disfonctionnement la pale attire l aimant mont dans le corps et actionne le contact au moyen d un simple levier CARACT RISTIqUES Corps usin dans la masse vitant les fuites Choix de pal...

Страница 10: ...e conduit M25 x 1 5 IECEx Bo tier rev tement poxy Palette pleine mouvement 180 sp cifique Fourni avec PV contr le d bit Haute pression 345 bar uniquement version inox Palette charni re version avec br...

Страница 11: ...c der 70 C Des conducteurs et une travers e de c ble 95 C nominal seront utilis s Note le d tecteur est d sactiv et les contacts en positions normales quand le d bit est inexistant 4 S assurer que le...

Страница 12: ...4 5 Tuyau 38 1mm 1 5 32 17 15 8 Tuyau 50 8mm 2 65 32 30 20 23 13 10 6 Tuyau 76 2mm 3 210 105 100 50 120 70 60 30 60 48 30 20 Tuyau 101 6mm 4 400 200 190 90 195 140 90 70 135 100 60 50 65 50 30 20 Tuya...

Страница 13: ...sellos que se puedan romper En su lugar una paleta de libre movimiento atrae a un im n al cuerpo del metal s lido actuando el contacto de un nivel de alarma CARACTERISTICAS Cuerpo a prueba de fugas E...

Страница 14: ...BSPT hembra de 1 1 2 3 81 cm M25 x 1 5 conexi n de conducto IECEx Alojamiento con epoxi Paleta con completo desplazamiento Informe de test de caudal Presi n alta 5000 psi 345 bar solo con cuerpo en SS...

Страница 15: ...ruptor se desactiva y los contactos estan en condicion normal cuando no haya caudal en la linea 4 Asegurarse que las conductos o cables est n correctamente sellados Los componentes el tricos deben man...

Страница 16: ...0 700 520 330 725 500 340 240 500 400 240 190 310 250 150 120 Tuberia 10 2400 1300 1100 600 1850 1200 870 570 1200 850 570 400 875 700 410 330 650 525 310 250 Tuberia 12 3450 1900 1600 900 2700 1750 1...

Отзывы: