MULTI GAS LEAK DETECTOR

 

 

 

 

ME-LOKATOR VL30 – REFRIGERANT GASES

 

                                                                                                          

PAGE  |  

2

 

LOKATOR VL 30   EN 

INTRODUCTION 

 

The LOKATOR VL30 Leak Detector has been designed for leak testing by direct sniffing on potential points of leakage. 
 
The LOKATOR VL30 Detector is equipped with a Detection Cell for refrigerant gases, HFO, HFC and HC. 
(R134a, R1234ze, R32, R290, R410, R600 and CUSTOM) 

 

LOKATOR VL30 can be operated intermittently or continuously on a production line. Optimal operating temperature between 10 °C and 
35 °C. Choose a clean, dry place, away from rain or splashing. Avoid corrosive or salt environments. 
 
 

GENERAL SAFETY INSTRUCTIONS 

 

•  Proper  use  for  the  intended  purposes: The  LOKATOR  VL30  should  only  be  used  for  leak  detection  method  described  in  this 
manual. The appliance is a gas leak detector and should not be used for measuring or controlling ambient air. In the event of improper 
use and / or control, the user or third parties may be exposed to hazards. Any deviations from the intended use described in this manual 
result in warranty restrictions and manufacturer's liability for damage. 
 
• Personnel and user: The LOKATOR VL30 may only be operated by qualified personnel trained for these activities. The contents of this 
manual must be explicitly communicated to the user and the user agrees to follow the instructions to ensure the correct functioning of the 
detector. 
  
• Surrounding environment: The LOKATOR VL30 should not be used in environments at risk of explosion and / or other hazardous 
environments. Smoking is prohibited in the surrounding area of LOKATOR VL30. The environment of use and the storage environment 
must be free from contamination and contamination and must in particular be protected against the influence of chemical substances such 
as silicones. Silicon and sulfur-containing media or inorganic impurities, oils, greases and liquids that evaporate can cause poisoning 
phenomena on the gas sensor that may alter the sensitivity and / or selectivity of the sensor. Reduced sensitivity, unstable calibration or 
false detection may be a possible consequence. 
  
• Commissioning and operation: Connecting the device to the socket must only be done by connecting a right cable. The appliance 
must only be repaired by the after-sales service. Any unauthorized intervention threatens the safety, the correct operation of the device 
and restricts the rights to guarantee. The connection cable between the device and the hand-held sensor must be guided in such a way 
as to avoid the risk of tripping for the operator and the rapid deterioration of the cable. 
 
• Emergency stop circuit: In case of emergency, put the LOKATOR VL30 off by pressing the power switch located on the rear of the 
housing and pull the plug. LOKATOR VL30 turns off immediately. 
 

• 

Shock: Before opening the unit, turn off the system and disconnect the power plug. Servicing, maintenance and repair work should only 

be carried out by the manufacturer's after-sales service or by specialists authorized by the manufacturer. 
 
• Ventilation: Ensure that the ventilation devices on the LOKATOR VL30 and accessories are operable. Clogged grids and ventilation 
slots may cause overheating, causing malfunction or damage to the unit. 

 

• Repairs, cleaning and maintenance: Interventions on the device as well as maintenance and repair work has only the right to be 
conducted by the manufacturer after-sales service or by specialists authorized by the manufacturer. Failure to observe this could result in 
damage to the unit. Any unauthorized intervention exposes the user to a risk, threatens the safety of the device and restricts the warranty 
rights. The activities described in the chapter "MAINTENANCE" are an exception. 
 
• Sensitive electronics: The sensor must always be connected or disconnected when the LOKATOR VL30 is off. The suction unit contains 
a suction system, avoid vibrations or shocks that may damage the system. 
  
Accessories / Spare parts: Use only the accessories and spare parts from the manufacturer. 

 

 

Содержание Lokring LOKATOR VL30

Страница 1: ...LOKATOR VL30 MULTI GAS LEAK DETECTOR INSTRUCTION MANUAL LOKATOR VL30 REF REV 1 0...

Страница 2: ...DETECTION LIGHT RAMP and SOUND SIGNAL 8 5 2 2 DETECTION SCREEN 9 5 3 LEAK REASEARCH DETECTION 10 5 3 1 LEAK RESEARCH PROCEDURE 10 5 3 2 ZEROTTING STABILITY 10 5 3 3 SATURATION CONTAMINATION CONTROLE...

Страница 3: ...ing phenomena on the gas sensor that may alter the sensitivity and or selectivity of the sensor Reduced sensitivity unstable calibration or false detection may be a possible consequence Commissioning...

Страница 4: ...mer Adjustable sound volume Indication of environmental contamination SELF CHECKING Permanent self checking Self checking of the Detection Cell Short circuit protection in the double plug cable COMMUN...

Страница 5: ...mains power socket 110v to 250v 50 60Hz 3 2 3 LEFT PANEL OF ELECTRONIC UNIT 1 Logic output DB9 socket 1 Ready to Detect 2 Busy 3 Error 4 Detection 5 Detec Threshold 6 Contamination 7 N A 8 GND 0v 9 12...

Страница 6: ...ows The detection of all the refrigerant gases currently used HFC HFO and Mixture Detection of the R600 R290 MINIMUM SENSITIVITY 1234ze 0 3 g yr MINIMUM SENSITIVITY R134a 0 3 g yr MINIMUM SENSITIVITY...

Страница 7: ...50v 50 60 Hz Earth Mains Plug and fuse of 500 mA are located on the back of the cabinet consumption 25 W approx 4 1 4 OPERATION WITH INCORPORATED BATTERIES PACK As an option the LOKATOR VL30 Detector...

Страница 8: ...he front panel of the cabinet lights up to indicate Mains power Wait 15 seconds and press the push button on the front panel for at least 2 seconds The green LED on the front panel lights up to indica...

Страница 9: ...efully do not hit it do not knock it down A circular seal protects the block head against shocks At rest hang the detection block on the support provided with the detector A fiber filter after the sem...

Страница 10: ...N CONTAMINATION of the cell x10 5 2 2 DETECTION SCREEN 1 Profile gas in use ex Profile A R32 2 Profile detection threshold in use 3 CALIBRATION Menu 4 Battery level display BATTERY Option 5 Select and...

Страница 11: ...e up the shape required by the user However avoid bending the tube into excessively sharp angles 5 3 2 ZEROTTING STABILITY With a new Sensor the manipulation of the Detection Probe can cause the zero...

Страница 12: ...AKEN BEFORE CALIBRATION PROCEDURE If the calibrated leak is adjustable pressure check the pressure corresponding to the calibration value During the calibration procedure move the probe smoothly Posit...

Страница 13: ...the detector 6 OPTIONS MENU The LOKATOR VL30 has 4 options screen OPTION 1 OPTION 2 OPTION 3 and OPTION 4 It is accessed by selecting OPTIONS 6 1 OPTION 1 PROFILE A SELECTION OF THE TYPE OF GAS SET TO...

Страница 14: ...ION Set the maximum degassing time of the LOKATOR VL30 after detection OFF the degassing time depends on the leak detected Degassing from 0s to 60s max 5s 30s the maximum degassing time is that set De...

Страница 15: ...cable in poor condition may have WIRES CUT INSIDE Replace the cable if necessary 4 Restart the detector by pressing the start button approx 2s 5 If the ERROR PROBE message persists the most common cau...

Страница 16: ...ction pipe The fiber filter mounted at the entrance to the Detection of Cell is replaceable by unscrewing the sniffing pipe This filter must be changed regularly and as soon as necessary 8 3 PERIODIC...

Страница 17: ...MULTI GAS LEAK DETECTOR ME LOKATOR VL30 REFRIGERANT GASES PAGE 16 LOKATOR VL 30 EN 10 CE DECLARATION...

Страница 18: ...7 LOKATOR VL 30 EN 11 TECHNICAL DATA Warm up time 180 sec Reaction time 1 sec Operating temperature 10 C 40 C Interface DB9 Logical signal output 0 V 5 V Power supply 110 V 250 V 50 60 Hz Power consum...

Отзывы: