PAGE: 9
LP-41 REV: 3/1/03
SSVH MODEL PERFORMANCE AND SET-UP INFORMATION
The SSVH models are available in the 90,000 BTU/hr, 130,000, and 199,000 BTU/hr. firing rates. The illustration on
page 43
show the
location of the heat exchanger and other ports. For maximum output, the bronze circulator provided must be attached between the hot
outlet and cold inlet as shown on
page 22
. For complete SSVH information and sizing, refer to
pages 42 and 43
.
CONTROL DESCRIPTION
The fully integrated water heater control is an all electronic, fully automatic controller which will provide many years of trouble free ser-
vice. The control requires no periodic maintenance and includes a built-in microprocessor which performs a number of diagnostic tests
to verify proper appliance and control operation. Should an unsafe condition occur, the burner will shut down and the appropriate status
indicators will illuminate indicating the need for service. Consisting of two printed circuit board assemblies, the controller's main board
is attached to inside left of the shroud while the display board is mounted to the front top of the shroud. This arrangement simplifies
access to the user adjustments while enhancing the visibility of the temperature display and status indicators. A power step-down
transformer and blower pressure switch are also mounted on the inside left of the shroud. The controller display functions include a
high visibility three digit LED readout which is used to display the actual water temperature within the tank along with the programmed
desired water temperature (set point temperature). Nine individual LED indicators are also mounted on the display board which are
used to determine the operating status of the appliance and provide assistance when troubleshooting any problems which may occur.
All indicators are of the solid state variety and should last for the life of the appliance. The controller has sufficient built-in memory to
retain the programmed temperature set point in the event input power is ever interrupted. The final component of the control system
includes a temperature sensing probe which is threaded into the side of the tank. This probe is of unique construction in that both the
temperature sensing/control and safety limit functions are performed by this single device. All probe components are of solid state con-
struction to provide extended operational life.
START UP PROCEDURE
1.
Make sure that the Voyager has been installed to these instruction procedures; along with all applicable province and local
codes;
2.
Make sure all gas piping and connections have been verified and inspected by all applicable inspectors. Turn on gas supply.
Insure that the gas line and the LP tank, if applicable, have been properly purged. Failure to properly purge the gas lines will
result in failure to operate;
3.
Make sure that the cold water supply has been turned on and that the Voyager is completely filled with water. Verify this by
opening a hot water faucet, and allowing water to flow until all air is removed and a clear water flow is present;
4.
Turn on electrical supply;
5.
The control will first display "102", then "88.8", which is the control display test; and finally the actual tank temperature at the
probe.
SET POINT ADJUSTMENT PROCEDURE
The three digit LED display will illustrate actual water temperature within the tank under normal operating conditions. However, this
display is also used to indicate the temperature set point when in the programming mode; and also ignitor amp draw and flame current.
The controller has a temperature set point range 70 degrees F. to 160 degrees F. The factory set point is 118 degrees F.
VERY IMPORTANT NOTE:
POWER MUST BE APPLIED TO THE CONTROLLER PRIOR TO ANY PROGRAMMING OPERATIONS.
Содержание SSV100-45R
Страница 12: ...PAGE 12 LP 41 REV 3 1 03...
Страница 15: ...PAGE 15 LP 41 REV 3 1 03...
Страница 16: ...PAGE 16 LP 41 REV 3 1 03...
Страница 17: ...PAGE 17 LP 41 REV 3 1 03...
Страница 18: ...PAGE 18 LP 41 REV 3 1 03...
Страница 19: ...PAGE 19 LP 41 REV 3 1 03...
Страница 20: ...PAGE 20 LP 41 REV 3 1 03 TYPICAL VENTING...
Страница 21: ...PAGE 21 LP 41 REV 3 1 03...
Страница 22: ...PAGE 22 LP 41 REV 3 1 03...
Страница 23: ...PAGE 23 LP 41 REV 3 1 03...
Страница 24: ...PAGE 24 LP 41 REV 3 1 03...
Страница 25: ...PAGE 25 LP 41 REV 3 1 03...
Страница 29: ...PAGE 29 LP 41 REV 3 1 03 PARTS ILLUSTRATIONS AIR INLET ADAPTER NI110 AIR INLET MANIFOLD A5000...
Страница 30: ...PAGE 30 LP 41 REV 3 1 03 GASKET AIR INLET G5030 GAS ORIFICE UNION GGU5...
Страница 32: ...PAGE 32 LP 41 REV 3 1 03 GASKET BURNER MOUNTING FLANGE G5010 BURNER MOUNTING FLANGE 7000 616...
Страница 33: ...PAGE 33 LP 41 REV 3 1 03 GAS VALVE GV1000 AIR INLET CONNECTOR F3000...