PAGE: 44

LP-41   REV:  3/1/03

VERY IMPORTANT!!!

THIS VOYAGER HAS THE NEW 1200 BOARD AND BLOWER SYSTEM!  THE ADDITIONAL FEATURES ARE LISTED BELOW:

1.

THE BOARD WILL DETECT PROPER POLARITY BY ILLUMINATING THE GREEN LED LIGHT LOCATED ON THE LOWER RIGHT 
CORNER OF THE BOARD.  NO LIGHT MEANS IMPROPER POLARITY!

2.

THE BLOWER CABLE AND THE CURRENT LIMITER HAVE BEEN ELIMINATED.

3.

THE LED DISPLAY IS FIVE TIMES BRIGHTER; GIVING GREATER VISIBILITY IN BRIGHT LIGHT.

4.

THE PUSH BUTTON IN THE FRONT OF THE CABINET ALLOWS THE USER TO READ IGNITOR DRAW IN 
AMPS (2.5 - 3.5), AND FLAME QUALITY IN MICRO AMPS (4.5 - 5.1).  TO READ IGNITOR DRAW, WAIT FOR THE LED LIGHT FOR THE 
IGNITOR TO COME ON, THEN SIMPLY PUSH THE BUTTON IN ON THE FRONT OF THE CABINET.  TO READ FLAME QUALITY, WAIT 
FOR THE GAS VALVE TO BE ACTIVATED AND THE IGNITOR LIGHT TO GO OFF, THEN SIMPLY PUSH IN THE BUTTON ONCE.  THIS 
WILL TAKE PLACE IN THE NORMAL OPERATING SEQUENCE IN A HEAT CYCLE.

5.

THE 1200 BOARD AND BLOWER SYSTEM PARTS ARE NOT INTERCHANGEABLE WITH THE VOYAGER PARTS (1000 SYSTEM) 
PREVIOUS TO THE 1200 SYSTEM.  PARTS FOR THE OLD 1000 VOYAGER SYSTEM ARE STILL AVAILABLE THROUGH OUR 
STANDARD DISTRIBUTION.

MOST COMMON VOYAGER INSTALLATION CONCERNS

VENTING:

VENT LENGTH TOO LONG - OVER 85’
VENTING NOT PITCHED PROPERLY - CONDENSATE BUILD UP IN VENT
EXHAUST GAS RE-CIRCULATION - VENT TERMINALS NOT USED, WRONG FITTINGS USED, SIGHT PROBLEMS
BUSH IN FRONT OF VENT TERMINAL
INSIDE CORNER OF BUILDING FOR VENT LOCATION
OVERHANG WITH VENT UNDERNEATH
COMPOUND ROOF PITCH, OR ABOVE ROOF FIRE WALL
ADDITIONAL FITTINGS INSTALLED INTO TERMINALS
VENT SIZED FROM 3" TO  4" BY USING BUSHINGS - INSTEAD OF REDUCING COUPLING OR REDUCING ELBOW
VENT CHANGED FROM 3" TO 4" - WITHOUT GOING REQUIRED 10’ ON BOTH INTAKE AND EXHAUST
VENTING NOT CLEANED AND GLUED TOGETHER FOR PRESSURE TIGHT JOINTS
INTAKE AIR CONTAINING EXHAUST FROM ANOTHER VENT OR APPLIANCE

GAS SUPPLY:

GAS PRESSURE TOO LOW - NEED 7" GAS PRESSURE UP TO 14" GAS PRESSURE
GAS METER TOO LOW IN CAPACITY
GAS REGULATOR NOT SIZED PROPERLY - TOO LOW IN CAPACITY
GAS PIPE TOO SMALL - ¾" MINIMUM GAS SUPPLY SIZE
GAS REGULATOR TOO CLOSE TO APPLIANCE - NEED 10’ OF PIPE FOR EVERY 200,000 BTU’S PER HOUR
GAS REGULATOR WITH LONG VENT OR BLEED VENT ORIFICE - REGULATOR SLOW TO RESPOND
GAS METER RESTRICTION, OR IN NEED OF REPAIR/REPLACEMENT
GAS SUPPLY PRESSURE DROPS BELOW 3½" WHEN APPLIANCE FIRES

ELECTRICAL:

APPLIANCE NOT GROUNDED
ELECTRICAL POLARITY REVERSED - FLAME WILL LIGHT BUT GO BACK OUT IN 4-6 SECONDS VOLTAGE TOO LOW OR TOO HIGH
APPLIANCE CYCLES, BUT NO IGNITION - LOOK FOR GLOW  FROM IGNITOR, IF NOT, REPLACE IGNITOR

PLUMBING:

SSVH MODELS WITHOUT RE CIRCULATING PUMP INSTALLED & WITHOUT WIRING IN PARALLEL WITH HEATING CIRCULATOR
DIELECTRIC UNIONS INSTALLED - RUSTY WATER

CONDENSATE:

CONDENSATE LINE NOT PITCHED TO DRAIN
CONDENSATE LINE NOT DRAINING DUE TO LONG RUN WITHOUT VENT
CONDENSATE PUMP NOT WORKING
CONDENSATE TRAP PLUGGED WITH PVC SHAVINGS

BURNER:

EXTREMELY LOUD BANG ON IGNITION - BURNER FAILED OR END CAP OFF
RED BURNER DECK AS SEEN THROUGH VIEW PORT - GAS VALVE NEEDS ADJUSTMENT, PAGE 38

GAS VALVE:

PUFFING ON IGNITION - ADJUST GAS VALVE, SEE PAGE 38
LOUD POP ON IGNITION, THEN RUNNING SMOOTH - ADJUST GAS VALVE, SEE PAGE 38
HUFF AND PUFF DURING OPERATION - ADJUST GAS VALVE, SEE PAGE 38
RUNNING GREAT BUT INTERMITTENTLY HUFFING OR POPPING - CHECK FOR RE-CIRCULATION UNDER VENTING

Содержание SSV100-45R

Страница 1: ...AS FIRED WATER HEATING COMBINATION APPLIANCE ANSI Z 21 10 3 MANUFACTURED BY HEAT TRANSFER PRODUCTS INC P O BOX 429 120 BRALEY ROAD EAST FREETOWN MA 02717 TEL 1 508 763 8071 and outside of MA 1 800 323...

Страница 2: ...6 SSV130 80R 23 1 4 230 Lbs 32 SSV130 45R 23 1 4 175 Lbs 32 SSV100 45R 23 1 4 175 Lbs 32 SSV90 45S 23 1 4 175 Lbs 32 74 72 27 1 4 27 1 4 42 1 2 72 42 1 2 42 1 2 74 42 1 2 42 1 2 FIRST HOUR VENT RECOVE...

Страница 3: ...esult in damage to the surrounding areas or to the lower floors of the building A water heater should always be located in a area with a floor drain or installed in a drain pan suitable for water heat...

Страница 4: ...be performed by a qualified licensed electrician and in accordance with National Electrical Code or to the applicable local codes and standards The electrical requirements are for standard 120 volts 6...

Страница 5: ...as per local and national standard plumbing codes It is important that the piping must be clean and free from burs debris ragged ends and particles of PVC For exhaust piping lower pipe on the right o...

Страница 6: ...5 for ABS or ASTM F 441 for CPVC and fittings to ASTM D2661 D3311 for ABS and ASTM F 439 for CPVC the balance of exhaust piping and all of intake piping use standard 3 PVC sch 40 or 3 ABS schedule 40...

Страница 7: ...FEET FOR EACH ELBOW TOTAL FRICTION LOSS FOR ELBOWS GRAND TOTAL VENT LENGTH FEET WITH FITTING FRICTION LOSS ADDED 12 2 5 10 22 20 2 5 10 30 20 3 5 15 35 20 4 5 20 40 20 5 5 25 45 20 6 5 30 50 20 7 5 3...

Страница 8: ...the entire intake system providing it conforms to ASTM F 891 and is cemented together using above materials never use foam core pipe for the exhaust pipe VERY IMPORTANT SSV100R SSV130R MODELS ONLY Al...

Страница 9: ...g any problems which may occur All indicators are of the solid state variety and should last for the life of the appliance The controller has sufficient built in memory to retain the programmed temper...

Страница 10: ...g the set point button when power is applied to the control Shut off power to the control Next hold in the set point button Now reapply power to the control Using the set point button the value of the...

Страница 11: ...the set point to 70 degrees F DO NOT turn off electrical power If there is no danger of freezing follow the Shutdown Procedure FAILURE TO OPERATE Should the burner fail to light the control will perfo...

Страница 12: ...PAGE 12 LP 41 REV 3 1 03...

Страница 13: ...g ori fices This is only a guide to correct orifice sizing If orifices are drilled the result will be poor ignition a VOIDED WARRANTY severe bodily injury death and or explosion All orifices must be o...

Страница 14: ...UTPUT IS ENERGIZED POWER APPLIED TO BLOWER IGNITOR MONITORS IGNITOR ELEMENT OUTPUT ON WHEN OUTPUT IS ENERGIZED POWER APPLIED TO IGNITOR 24V MONITORS INCOMING VOLTAGE FROM THE ON WHEN SECONDARY VOLTAGE...

Страница 15: ...PAGE 15 LP 41 REV 3 1 03...

Страница 16: ...PAGE 16 LP 41 REV 3 1 03...

Страница 17: ...PAGE 17 LP 41 REV 3 1 03...

Страница 18: ...PAGE 18 LP 41 REV 3 1 03...

Страница 19: ...PAGE 19 LP 41 REV 3 1 03...

Страница 20: ...PAGE 20 LP 41 REV 3 1 03 TYPICAL VENTING...

Страница 21: ...PAGE 21 LP 41 REV 3 1 03...

Страница 22: ...PAGE 22 LP 41 REV 3 1 03...

Страница 23: ...PAGE 23 LP 41 REV 3 1 03...

Страница 24: ...PAGE 24 LP 41 REV 3 1 03...

Страница 25: ...PAGE 25 LP 41 REV 3 1 03...

Страница 26: ...HARNESS FROM THE GAS VALVE BY PRESSING ON THE TABS ON THE TOP AND BOTTOM OF THE PLUG AND PULLING 13 REMOVE THE TWO GREEN GROUNDING WIRES FROM THE TOP REAR OF THE BLOWER BY TAKING OUT THE GREEN GROUNDI...

Страница 27: ...PART 99MA 5 RE INSERT THE BURNER WITH THE FLAT SIDE OF THE FLANGE FACING DOWN 6 REPLACE THE BLOWER OUTLET FLANGE GASKET WITH A NEW GASKET BE SURE THAT BOTH SIDES OF THE GASKET ARE SPRAYED WITH PERMAT...

Страница 28: ...7 16 DEEP SOCKET 19 PLACE GAS ORIFICE ON TOP OF THE SPLIT UNION WITH HOLE FACING UP AS SHOWN BELOW 20 RE CONNECT THE GAS VALVE TO THE AIR INLET MANIFOLD BY TURNING THE UNION COUNTER CLOCKWISE AND TIG...

Страница 29: ...PAGE 29 LP 41 REV 3 1 03 PARTS ILLUSTRATIONS AIR INLET ADAPTER NI110 AIR INLET MANIFOLD A5000...

Страница 30: ...PAGE 30 LP 41 REV 3 1 03 GASKET AIR INLET G5030 GAS ORIFICE UNION GGU5...

Страница 31: ...PAGE 31 LP 41 REV 3 1 03 GAS ORIFICE 01000 AIR ORIFICE A3001 1 0 SIZE A3002 1 125 SIZE A3003 1 375 SIZE FLAME RECTIFICATION PROBE PSE TF1...

Страница 32: ...PAGE 32 LP 41 REV 3 1 03 GASKET BURNER MOUNTING FLANGE G5010 BURNER MOUNTING FLANGE 7000 616...

Страница 33: ...PAGE 33 LP 41 REV 3 1 03 GAS VALVE GV1000 AIR INLET CONNECTOR F3000...

Страница 34: ...PAGE 34 LP 41 REV 3 1 03 110V IGNITOR SURFACE IGNITER 0206FF003 GASKET BURNER MOUNTING FLANGE WHITE G5040 GASKET BLOWER OUTLET FLANGE G5020...

Страница 35: ...ETWEEN THE GAS VALVE AND AIR INLET REMOVE OLD GAS ORIFICE 5 AND INSTALL THE NEW GAS ORIFICE IN THE UNION THAT CORRESPONDS TO THE UNIT MODEL NUMBER AND FUEL BEING USED SEE KIT CONTENT LIST FOR THE CORR...

Страница 36: ...HE VOYAGER 2 REMOVE THE DOOR FROM THE VOYAGER CABINET 3 SHUT OFF THE GAS VALVE BY TURNING THE BLUE KNOB ON THE VALVE TO THE OFF POSITION 4 SHUT OF THE GAS SUPPLY TO THE VOYAGER 5 BREAK THE UNION ON TH...

Страница 37: ...RS AVAILABLE THEN FOLLOW INSTALLATION PROCEDURE 2 IF NO MANOMETERS ARE AVAILABLE USE INSTALLATION PROCEDURE 1 PROCEDURE 1 1 RE CONNECT THE GAS VALVE WIRING HARNESS TO THE GAS VALVE 2 SLIDE THE GAS VAL...

Страница 38: ...ND THE GAS VALVE WIRING HARNESS IS PLUGGED INTO THE GAS VALVE AND INTO THE CONTROL BOARD 2 TURN THE ADJUSTMENT SCREW UNDER THE BRASS CAP YOU REMOVED IN STEP 8 ABOVE TURN ONE FULL TURN CLOCKWISE WITH A...

Страница 39: ...E STEADIES 2 PUT THE GAS VALVE ADJUSTMENT SCREW COVER BACK IN PLACE AND TIGHTEN 3 PUT THE VOYAGER CABINET DOOR BACK INTO PLACE PROCEDURE 2 1 REMOVE THE OUTLET PRESSURE TAP PLUG FROM THE RIGHT SIDE OF...

Страница 40: ...RE CONNECT THE SUPPLY GAS PIPING TO THE VALVE 8 TURN ON THE GAS TO THE VOYAGER 9 TURN THE BLUE KNOW ON THE GAS VALVE TO ON 10 REMOVE THE SMALL ROUND BRASS PLUG FROM THE GAS VALVE BY TURNING IT COUNTE...

Страница 41: ...NOT LIGHT OFF TURN THE ADJUSTMENT SCREW TWO FULL TURNS COUNTERCLOCKWISE 14 SHUT THE VOYAGER DOWN THEN START IT UP AGAIN LET IT RE LIGHT IF THE IGNITION WAS GOOD THE VALVE NEEDS NO FURTHER ADJUSTMENT...

Страница 42: ...ON GASES AND CONNECTION OF A BRONZE CIRCULATOR BETWEEN DOMESTIC HOT WATER OUTLET DOMESTIC COLD WATER INLET NOTE IT IS VERY IMPORTANT TO FOLLOW EITHER LOCAL OR FEDERAL PLUMBING CODES WHEN INSTALLING AN...

Страница 43: ...400 95 200 119 000 124 500 10 85 000 113 250 140 000 140 000 FOR SSVH 130 MODELS ONLY FOR SSVH 199 80 MODELS ONLY NOTE THE VOYAGER MUST BE SET 25 DEGREES F ABOVE THE SYSTEM TEMPERATURE THE ABOVE CHAR...

Страница 44: ...S VENT SIZED FROM 3 TO 4 BY USING BUSHINGS INSTEAD OF REDUCING COUPLING OR REDUCING ELBOW VENT CHANGED FROM 3 TO 4 WITHOUT GOING REQUIRED 10 ON BOTH INTAKE AND EXHAUST VENTING NOT CLEANED AND GLUED TO...

Отзывы: