1. Standard length of connection pipe
● 5m, 7.5m, 8m.
2. Min. length of connection pipe is 3m.
3. Max. length of connection pipe and max.
high difference.
4. The additional refrigerant oil and refrigerant charging required after prolonging
connection pipe
●
After the length of connection pipe is prolonged for 10
m
at the basis of standard length
,
you should add 5ml of refrigerant oil for eac
h
additional 5m of connection pipe.
●
Thecalculation methodof additional refrige
r
ant charging amount (onthe basis of liquid
pipe):
Additional refrigerant charging amount = prolonged length of liquid pipe (m)
x additional refrigerant charging amount per meter
● Basing on the length of standard pipe, ad
d
refrigerant according to the requirement
as shown in the table. The additional refrigera
nt charging amount per meter is di
fferent
according to the diameter of liquid pipe. Se
e the following sheet.
Additional refrigerant charging amount for
R410 A
Diameter of connection pipe
Extra refrigerant charge
Liquid pipe(in)
Gas pipe(in
)
Cooling and heating(g/m)
15/64
3/8 or 1/2
15
20
15/64 or 3/8
5/8 or 3/4
15
50
15/32
3/4 or 7/8
30
120
5/8
1 or 1 1/4
60
120
3/4
-
250
250
55/64
-
350
350
3
6
Cooling only(g/m)
Cooling
capacity
Max lenght
of connection
pipe(m)
Max height
difference
(m)
9000Btu/h
(2637W)
15
5
12000Btu/h
(3516W)
20
10
18000Btu/h
(5274W)
25
10