- 89-
P12.01
Multi-point VF Frequency
1(F0)
0.00Hz
~
multi-point VF curve F1(P12.03)
0.00Hz
☆
P12.02
Multi-point VF Voltage 0(V0)
0.0%
~
100.0%
0.0%
☆
P12.03
Multi-point VF Frequency
1(F1)
multi-point VF curve F0(P12.01)
~
multi-point
VF curve F2(P12.05)
50.00Hz
☆
P12.04
Multi-point VF Voltage 1(V1)
0.0%
~
100.0%
100.0%
☆
P12.05
Multi-point VF Frequency
1(F2)
multi-point VF curve F1(P12.03)
~
multi-point
VF curve F3(P12.08)
50.00Hz
☆
P12.06
Multi-point VF Voltage 2(V2)
0.0%
~
100.0%
100.0%
☆
P12.07
Multi-point VF Frequency
3(F3)
multi-point VF curveF2(P12.05)
~
600.00Hz
50.00Hz
☆
P12.08
Multi-point VFVoltag
e 3(V3)
0.0%
~
100.0%
100.0%
☆
P12.09
Torque boost
0%
~
200%
0% is automatic torque boost
0%
☆
Automatic torque boost
When P12.09=0=Automatic torque boost,inverter will automatically compensate output voltage to improve
torque in low frequency as per actual load ,it is useful for linear VF curve
Manual torque boost
When P12.09 not 0,it means manual torque output.Output frequency 0 torque increasing
value=p12.09*motor stator resistance *rated excitation current,,increasing value will be gradully decreased
as frequency increase ,if higher than 50% of motor rated frequency,increasing value will be zero
Notice:manual torque boost is useful to linear and power curve
P12.11
Slip compensation gain
0
~
200%
It is used to compensate the speed drop of
the asynchronous motor VF control with load,
and improve the speed control accuracy.
Please adjust according to the following
principles:
Increase the setting when the motor
speed is lower than the target value
100%
☆