Appendix A Modbuscommunication protocol IR610 high performance vector control frequency inverter user manual
- 168 -
Number of function
code
Including the register address (2Byte), the number of registers n(2Byte)
and the register content (2nByte), etc.see A3 in detail
CRC CHK low level
It indicates the replying data or the data waiting to
write-in. CRC 16 check value,During the transmission, high bit is put in
frontand low bit is at the back.see detail in A.5 Chapter
CRC CHK high level
FRAME END
More than 3.5 byte transmission time
A.3 Command code instruction
A.3.1 Command code 0x03Read multiple registers or status words
Request PDU
Command code
1byte
0x03
initial address
2byte
0x0000
~
0xFFFF(high 8
bit in front)
Number of registers
2byte
0x0001-0x0010 (1
~
16,high 8 bit in front)
Response PDU
Command code
1byte
0x03
Initial address
1byte
2n
(
n means Number of
registers
)
Number of registers
2* nbyte
Register value high 8 bit
in front,first send initial
address
’register value
Wrong PDU
Command code
1byte
0x83
Abnormal code
1byte
See A.4Abnormal
response information
Currently Modbus protocol 0x03 command code does not support cross-group read multiple function
codes, it will be wrongif more than the current group of function code number
A.3.2 Command code 0x06 write single registers or status word command codes
Request PDU
Command code
1byte
0x06
Initial address
2byte
0x0000
~
0xFFFF(high 8