- 71-
P05.08
AO1 output gain
-10.00
~
10.00
1.00
☆
The output error of AO1 can be corrected by P05.07 and P05.08, or the mapping relationship between signal
source and actual output can be changed. The formula is:
AO.c = P05.07 + P05.08 × AO.p AO.c: the actual output of AO1;
AO.p: AO1 Value before correction and
AO.c, AO.p, 100.0% of P05.07 corresponds to 10V or 20mA.
r05.09
AO2 actual value
0.0%
~
100.0%
-
●
P05.10
AO2 output function signal
selection
Same as P05.02 function description
0
☆
P05.11
AO2 output offset
-100.0%
~
100.0%
0.0%
☆
P05.12
AO2 gain
-10.00
~
10.00
1.00
☆
The output error of AO2 can be corrected by P05.11 and P05.12, or the mapping relationship between signal
source and actual output can be changed. The formula is:
AO.c = P05.11 + P05.12 × AO.pAO.c: the actual output of AO2;
AO.p: AO2 value before correction and
AO.c, AO.p, 100.0% of P05.11 corresponds to 10V or 20mA.
06 Group Multi-function Digital input
r06.00
DI port status
Bit0
~
Bit8 Correspond to DI1
~
DI8
Bit12
~
Bit15 Correspond to VDI1
~
VDI4
-
●
P06.01
DI1 Numeric input function
0
:
No function
1
:
FORWARD
2
:
Reverse/Forward and reverse switchover
3
:
Three wire control
4
:
Forward jog command
5
:
Reverse jog command
6
:
Terminal UP
7
:
Terminal DOWN
8
:
Clear up UP/DOWN offset
1
★
P06.02
DI2 Numeric input function
2
★
P06.03
DI3 Numeric input function
4
★