15
Connecting the CIU
CIU
GN/OR
SPEED
CONTROL
GN/SB
GN/Y
POT –
POT +
POT SIGNAL
0,5-2
k
Ω
2-10 k
Ω
(optional)
min
-120 rpm
max
+120 rpm
max
2 k
Ω
0,5-2
k
Ω
Engine control
See wiring diagram.
NO = Normally open
NC = Normally closed
Ignition key (system voltage OFF/ON)
NOTE!
Start current for the engine’s system voltage
(the control module) is 10 A. Make sure that other
components in the installation are dimensioned for this
current.
Start contact
Contact type, closing (NO), spring biased.
Stop contact
Contact type, closing (NO), spring biased.
Via parameter setting, it can become energized during
operation. In that case, use contact type closed (NC).
RPM-potentiometer
Nominal rpm minus 120 rpm:
0.3–1.9 V
(preset value 1.17 V)
Nominal rpm plus 120 rpm:
1.9–4.7 V
(preset value 4.5 V)
1500 / 1800 rpm contact
This function allows a change of frequency from 50 to
60 Hz.
Contact type two position.
Idle contact
Contact type two position.
Closed contact provides idling speed (900 rpm).
Speed droop contact
The contact must be closed to obtain speed droop.
Contact type two position.
Governor contact
Contact type two position.
Preheat contact
Contact type two position.
1.17 V
2.84 V
4.5 V
Nominal rpm
(1500/1800
rpm)
Nominal rpm
– 120 rpm
Nominal rpm
+ 120 rpm
Содержание TAD734GE