32
Table 4-7
Setting Item
Sub Item
Explanation
Output Voltage
--
Set output voltage (220Vac, 230Vac,
240Vac)
BYPASS SETTING
Bypass Voltage
Range
Set bypass voltage range: upper limit
(+10%, +15%, +20%) and lower limit
(-10%, -20%, -30%)
Bypass Frequency
Range
Set bypass Frequency range: upper limit
(+1Hz, +2Hz, +4Hz) and lower limit
(-1Hz, -2Hz, -4Hz)
Converter Mode
--
Set converter mode “Disable” or ”Enable”
ECO Mode
--
Set ECO mode “Disable” or ”Enable”
Bypass Mode
--
Set bypass mode “Disable” or ”Enable”
Auto-Restart
--
Set auto-restart “Disable” or ”Enable”.
After “Enable” is set up, once UPS
shutdown occurs due to low battery and
then utility restores, the UPS will return to
line mode.
Cold Start
--
Set cold start “Disable” or ”Enable”.
After “Enable” is set, the UPS can be
turned on without utility connection by
pressing Battery Start Button. Refer to
cold start operation for the details.
Battery Mode Delay
Time
--
Set system shutdown delay time in
battery mode (0~9990sec)
System Shutdown
Time
--
Set system shutdown time (0.2~99min)
System Restore
Time
--
Set system restore time (0~9999min)
Redundancy
--
Set total power and redundancy