Auto return to default
display screen
Return to default
display screen
(default)
If selected, no matter how users
switch display screen, it will
automatically return to default display
screen (Input voltage /output voltage)
after no button is pressed for 1
minute.
Stay at latest screen
If selected, the display screen will stay
at latest screen user finally switches.
20
Backlight control
Backlight on
(default)
Backlight off
22
Beeps while primary source
is interrupted
Alarm on (default)
Alarm off
23
Overload bypass:
When enabled, the unit will
transfer to line mode if
overload occurs in battery
mode.
Bypass disable
(default)
Bypass enable
25
Record Fault code
Record enable
Record disable (default)
26
Bulk charging voltage
(C.V voltage)
56.4V (default)
If self-defined is selected in program 5, this program can be
set up. Setting range is from 48.0V to 58.4V. Increment of
each click is 0.1V.
27
Floating charging voltage
54.0V (default)
If self-defined is selected in program 5, this program can be
set up. Setting range is from 48.0V to 58.4V. Increment of
each click is 0.1V.
29
Low DC cut-off voltage
42.0V (default)
If self-defined is selected in program 5, this program can be
set up. Setting range is from 40.0V to 48.0V. Increment of
each click is 0.1V. Low DC cut-off voltage will be fixed to
setting value no matter what percentage of load is connected.