25
SPECIFICATIONS
Table 1 Line Mode Specifications
Line Mode (Utility Bypass Mode)
Model
5KVA with 2 MPPTs
5KVA with 3 MPPTs
Input Voltage Waveform
Sinusoidal (utility or generator)
Nominal Input Voltage
230Vac
Maximum input current
40A
Maximum input inrush current
65A peak 100ms
Low Loss Voltage
170Vac± 7V(UPS); 90Vac± 7V(Appliances)
Low Loss Return Voltage
180Vac± 7V(UPS); 100Vac± 7V (Appliances)
High Loss Voltage
280Vac± 7V
High Loss Return Voltage
270Vac± 7V
Max AC Input Voltage
300Vac
Nominal Input Frequency
50Hz / 60Hz (Auto detection, 55Hz as boundary)
Low Loss Frequency
40± 1Hz
Low Loss Return Frequency
42± 1Hz
High Loss Frequency
65± 1Hz
High Loss Return Frequency
63± 1Hz
Output Short Circuit Protection
Line mode: Circuit Breaker
Battery mode: Electronic Circuits
Efficiency
>95% (Rated R load, battery full charged)
Transfer Time
10ms typical, 12ms maximum @50Hz (UPS);
20ms typical, 25ms maximum @50Hz (Appliances)
Power Limitation
Input Voltage
Output Power
Rated Power
50% Power
90V
170V
280V