![VOLTIMA VSI 104 Скачать руководство пользователя страница 78](http://html1.mh-extra.com/html/voltima/vsi-104/vsi-104_installation-and-operating-instructions-manual_1047700078.webp)
78
VOLTIMA VSI/VST Series
Protection
Protective
Trigger
Impact
Mains priority
and
Inverter
protection
mode
Earth-closing
protection
The inverter switches off when electrical
leakage occurs at load.
Low-voltage-alarm
An alarm is triggered when the battery is
discharged to about 10.5V.
Low-voltage-
protection
The inverter shuts down when the battery
is discharged to about 10,0V.
Surge- protection
The inverter switches off
when
overvoltage.
Overheating-
protection
The inverter switches off in case of
overheating.
Overload-
protection
The inverter switches off when the
charging power exceeds the rated power.
Short-circuit-
protection
The inverter switches off when an output
short circuit occurs.
Softstart -
Circuit
Gradual voltage
increases when
switching on the
inverter
Prevent failed cold starts.
Output that lowers
the voltage for a
short time and
restores it quickly
This prevents most shutdowns due to
short-term overload.
Automatic restart
The inverter automatically switches on
again as soon as the overload is over.
AVS - Protection
function
Time delay
Reconnection after a protective shutdown
is 20s. The time delay function prevents
the inverter from being damaged if faults
occur frequently in the AC mains supply.