6. TROUBLESHOOTING     

TV Interference 

You can sometimes get interference on TV & Radio receivers. This may be improved 
through use of a filter(s) but most problems occur because of Weak Signal to the TV. 
On  some  occasions  when  there  is  interference  on  every  station,  you  can  try  the 
following: 

 

Place the inverter farther from the TV and TV antenna and cable. 

 

Make sure the Inverter Casing is grounded to the Vehicle Ground(Chassis) 

 

Try  to  change  the  direction  of  TV  signals  cable  and  TV  antenna  to  reduce  the 
interference to minimum. 

 

Use screened antenna cable of higher quality. 

SYMPTOM 

POSSIBLE CAUSE 

SOLUTIONS 

ON/OFF switch is switched on, 

LED does not light. Buzzer is 

off. There is no AC voltage 

 

There is no voltage at the DC 

input Terminals 

 

1.  Check  the  continuity  of  the 

battery input circuit 

2. Check that the battery fuse is 

intact. Replace if blown 

3.  Check  that  all  connections  in 

the battery input circuit are tight 

Polarity  of  the  input  voltage  has 

been reversed that has blown the 

DC side fuses. 

Note:  Reverse  polarity  may

 

cause permanent damage)

 

 

Correct the polarity of the input 

connections  and  replace  the 

fuse. 

If  the  unit  does  not  work  after 

replacing  the  fuse,  the  unit  has 

been permanently damaged 

Call Technical Support 

Buzzer  alarm  is  sounded  1 

time. There is no AC voltage. 

1.Loose AC output connections. 

2.Short  circuit  of    AC  Output 

wiring. 

1.Tighten AC output connections 

2.Check  AC  wiring  for  short 

circuit.   

Buzzer  sounds  2  times 
and  Red  LED  blinks  2 
times 

every 

eight 

seconds

 

Voltage at the DC input 

terminals reads below; 

10.8±0.2VDC(12V version), 

21.6±0.4VDC(24V version), 

43.2±0.8VDC(48V version). 

1.Check that the battery is fully 

charged. Recharge if low. 

2. Check that the battery cables 

are  thick  enough  to  carry  the 

required 

current 

over 

the 

required length. Use 

thicker cables if required. 

3.  Tighten  connections  of  the 

battery input circuit 

Содержание KS2000P

Страница 1: ...put 5V 500mA Optional Variable speed DC fans Controlled by Temperature and Load Protection LED Indicator Audible Alarm 12V or 24V Models Input voltage range 15 25 Output voltage regulation 10 Output w...

Страница 2: ...y Bank 7 3 3 Battery wiring examples 7 8 3 4 Placement of the inverter 8 3 5 Mounting position of the inverter 9 3 6 Connections 9 4 Important Safety Instructions 9 10 5 Protection Feature 10 6 Troubl...

Страница 3: ...e sine wave inverter With pure sine wave motors start easier and run cooler As well some equipment may only operate properly with a pure sine wave inverter such as laser printers variable speed motors...

Страница 4: ...F switch via a communication cable H Hardwire Terminal Block 2500W to 6000W Note When the load current is 10A 2300W You must use the output terminal connection which can be found inside the AC output...

Страница 5: ...e is more than 45 the fan s rotational speed is 100 B DC Battery Terminals Connect the inverter to battery or other power sources Negative and Positive DC terminals should be kept insulated to protect...

Страница 6: ...or printed on most appliances and equipment In some cases a tool will be rated in amperes To convert from amps to watts multiply Amps x AC voltage Watts Eg 2 0 A x 230 V 460 Watts This formula yields...

Страница 7: ...st be capable of delivering to the inverter divide the load watts by ten For example a 500 watt appliance load will need 50 amps at 12 volts DC Using the 500 watts or 50 amps for 10 hours example as a...

Страница 8: ...clearance around the unit for air flow Do not place items on or over the inverter during operation Make sure that air is allowed to circulate freely around the unit A fan is helpful in the case where...

Страница 9: ...tions 1 Do not attempt to connect the output to any other power source including any AC mains 2 Make sure the opening to the ventilation fan and vent holes are not blocked 3 Avoid pulling on the cords...

Страница 10: ...cally shut off Input Over Voltage Protection When input voltage reach 15 5V 0 2V for 12V input inverter 31V 0 4V for 24V input inverter 62V 0 8V for 48V input inverter The Buzzer will sound 4 times an...

Страница 11: ...ntact Replace if blown 3 Check that all connections in the battery input circuit are tight Polarity of the input voltage has been reversed that has blown the DC side fuses Note Reverse polarity may ca...

Страница 12: ...harger alternator solar charge controller is below 15 V 30V 60VDC 3 Ensure that an un regulated solar panel or wind turbine is not used to charge a battery Buzzer sounds 5 times and Red LED blinks 5 t...

Страница 13: ...Open sealed lead acid battery Dimension L W H cm 17 15 5 5 21 15 7 21 15 7 37 5 15 7 2 36 22 9 29 22 9 Packing PCS CTN 12 6 6 4 2 2 KGS CTN 16 5 14 5 15 5 14 5 11 5 13 5 MEAS L W H cm 44 42 32 42 34 4...

Страница 14: ...dically with a dry cloth to prevent accumulation of dust and dirt At the same time tighten the screws on the DC input terminals 9 WARRANTY We guarantee this product against defects in materials and wo...

Страница 15: ...lash load power is less than 5 of rated power or standby AC ON Solid green Inverter s output is continuous Fault Turns red to show fault refer to Troubleshooting of Inverter Manual Connecting the Comm...

Страница 16: ...0 Ah 24V 6mm 1 Red 1 Black 20A 4 80Ah 48V 4mm 1 Red 1 Black 10A 4 40Ah 1500W 12V 10mm 2 Red 2 Black 35A 6 250Ah 24V 6mm 2 Red 2 Black 20A 6 125Ah 48V 4mm 2 Red 2 Black 10A 6 60Ah 2000W 12V 16mm 2 Red...

Отзывы: