LED C.
Charging status:
Green blinking: Bulk/ Absorption Charge
Green solid:
Float Charge
A. Remote Temperature sensor socket for battery
B. Output to battery or load.
C. Power ON / OFF switch.
D. Explanation of the DIP switches settings for Battery Type or charge
profile selection.
There are 6 DIP switches Up position is the On or Selected position.
Caution
Only one
switch is allowed to be set to ON (up position) at any one time.
If more than one switch set to ON, output will shut down and the orange B LED
will blink until selection has been corrected.
BATTERY CHARGER MODE
DIP 1 UP: AGM/GEL battery type. Absorption 14.1V, Float 13.2V.
DIP 2 UP: Wet battery type. Absorption 14.4V, Float 13.5V.
DIP 3 UP: Calcium-Calcium type. Absorption 15.5V, Float 13.8V.
DIP 4 UP: User defined 1 in which Absorption, Float Voltages and
Absorption time are set via Remote Display Module.
DIP 5 UP: User defined 2 in which Absorption, Float Voltages and
Absorption time are set via Remote Display Module.
BATTERY EQUALIZER MODE
DIP 6 UP: Battery Equalizer: Output V = ½ Input V.
VOLTAGE REDUCER MODE
All 6 DIP switches DOWN: Unit becomes a DC Voltage Reducer with
regulated 13.8V output.
E. Remote Display connecting / connector is RJ12.