Table with parameters
Parameter code Description
Value range
Factory setting
Unit
Parameter Menu CP
diF
Temperature step width
"1 - 30"
2
°C/°F
HSE
Set maximum temperature
"LSE - 99"
99
°C/°F
LSE
Set minimum temperature
"-55 - HSE"
-55
°C/°F
HC
Control mode (H = heat; C = cool)
"H/C"
H
/
If the temperature sensor fails, the compressor is shifted to the cycle
mode:
Ont
On t: Runtime for the switched-on phase
On t: Runtime for the switched-on phase of the cycle. 0
Minutes
OF t: Runtime for the switched-off phase of the cycle.
Ont=0;OFt=1: Compressor remains off.
OFt
Ont=1;OFt=0: Compressor is permanently on.
"0-250"
1
Minutes
Ont≠0;Ont≠0: Compressor runs in the cycle
with the times for the switched-on and -off phases as described above.
dOn
Delay time until the compressor starts
"0-250"
0
Seconds
dOF
Time interval between the
"0-250"
0
Minutes
dbi
The time interval between two consecutive comp. start processes
"0-250"
0
Minutes
OdO
Time delay of the output after the device switches on
"0-250"
0
Minutes
Parameter Menu diS
LOC
Button lock (n = buttons not blocked, y = buttons locked)
It is possible to program the parameters further
"n/Y"
n
/
PA1
User password
"0-250"
0
/
ndt
Display the decimal point: y = yes; n = no
"n/Y"
n
/
CA1
Calibrate temperature
"-12-12"
0
°C/°F
dro
Temperature unit (0 = °C, 1 = °F)
"0/1"
1
/
Parameter Menu CnF
H00
Selection of the sensor type (0 = PTC, 1 = NTC)
"0/1"
1
/
rEL
Device version
"/"
/
/
tAb
Parameter overview
"/"
/
/
The target value [SEt] should always be between the parameters [LSE] (lowest target value to be set) and [HSE] (highest target value to be set). For example, if [HSE] is set to 10, the
target value cannot be set higher.