26

Mynute 24m

8.2

CONNECTION OF AN EXTERNAL TIME CLOCK
AND ROOM THERMOSTAT (fig. 19A)

Isolate the appliance from the electrical supply.
Remove the appliance casing and PCB cover as
detailed in section 4.

Connect the time clock/room thermostat as shown
in diagram 219A. Vokera recommend the use of
“voltage-free” type controls. Should another type
of control be preferred, please contact the techni-
cal help-line for detailed advice and guidance.

Carry out the electrical checks as described in
7.11 prior to refitting the PCB cover and appli-
ance casing.

8.3

CONNECTION OF AN INTEGRAL TIME CLOCK

The Vokera integral time clock (Part no. 433) should
be installed as shown in diagram 19B.

If a room thermostat is to be connected, it should
be of the ‘voltage-free’ type and must be con-
nected ‘in series’ as shown in fig. 19A.

Fig. 19A

NOTE

Guidance on the recommended practice for the
installation of external controls, can be found in
CHeSS – HC1/HC2 (www.energy-
efficiency.gov.uk)

The external time-clock and/or room thermostat must be of the

“voltage-free” type and be wired as shown in the diagram.

The “link-wire” must be removed when additional controls are

connected to the appliance.

This appliance requires a permanent 230V electrical supply.

External

time-clock

Room

thermostat

Fusible 2AF

Neutral

Live

Black

Black

Black

Black

Brown

Blue

Fuse 2AF

Fig. 19B

Содержание Mynute

Страница 1: ...Mynute 24m Installation Servicing Instructions THESEINSTRUCTIONS TO BE RETAINED BY USER...

Страница 2: ...rical connections 13 Commissioning Page 5 1 Gas supply installation 15 5 2 The heating system 15 5 3 Initial filling of the system 15 5 4 Initial flushing of the system 15 5 5 Pre operation checks 15...

Страница 3: ...ler which by design incorporates electronic ignition circulating pump expansion vessel safety valve pressure gauge and automatic by pass It is produced as a room sealed category II2H3 appliance suitab...

Страница 4: ...tes Thereafter the boiler s output will either be increase to maximum or modulate to suit the setrequirement Whentheappliancereachesthedesiredtempera ture the burner will shut down and the boiler will...

Страница 5: ...s Pre charge pressure 1 0 bar 2 4 Dimensions Height 740 mm Width 400 mm Depth 332 mm Dry weight 31 kg 2 5 Clearances Left side 12 mm Right side 12 mm Top 150 mm from casing or 25 mm above flue elbow w...

Страница 6: ...Belowgutter drain pipe etc 75mm E Beloweaves 200mm F Below balcony car port roof etc 200mm G To the side of a soil drain pipe etc 150mm H Frominternal externalcornerorboundary 300mm I Aboveground roo...

Страница 7: ...suit Details of essential features of compartment cup board design including airing cupboard installations are given in BS 6798 This appliance is not suitable for external installation BS5440 PART 1 F...

Страница 8: ...ly this is sufficient however if the system has an unusually high water content it may be necessary to provide additional expansion capacity see 6 19 3 6 6 LOW PRESSURE SEALED SYSTEM An alternative me...

Страница 9: ...The gas meter as supplied by the gas supplier must be checked to ensure that it is of adequate sizetodealwiththemaximumratedinputofallthe appliances that it serves Installation pipes must be fitted i...

Страница 10: ...rgeneralguid ance only This appliance is a room sealed fan flued boiler consequently it does not require a permanent air vent for combustion air supply When installed in a cupboard or compartment vent...

Страница 11: ...e only to the standard 60 100mm concentric flue system The appliance flue outlet elbow can be rotated through 360 on its vertical axis In addition the flue may be extended from the outlet elbow in the...

Страница 12: ...irednumberofflueextensionsor bends uptothemaximumequivalentfluelength to the flue terminal using the clips screws and gaskets supplied fig 8 8A The interior trim should be fitted at this point Fig 8 B...

Страница 13: ...given to the fact that there is the possibility of a small amountofcondensatedrippingfromtheterminal ensure that the entire flue system is adequately supported use at least one bracket for each extens...

Страница 14: ...must always be level with or below that of the exhaust pipe Dependingonsiteconditionsitmaybepreferable to install the terminal assembly prior to fitting the twinfluepipes Markanddrilla130mmholeforthe...

Страница 15: ...andreturnconnections connect a 22 mm pipe to the inlet of each valve and tighten both nuts 4 6 3 SAFETY VALVE fig 6 Connect the safety valve discharge pipe to the safetyvalveoutletandtighten Thedischa...

Страница 16: ...ablethroughthecableanchorage fig 6 Connectthesupplycablewires earth live and neutral to their corresponding terminals on the terminal strip Ensure that the EARTH wire is left slightly longer that the...

Страница 17: ...GHTING Ensure the electrical supply to the appliance is switchedon Switchthetimeclockorprogrammer iffitted toan on positionandensureallexternal controls are also calling for heat SECTION 5 COMMISSIONI...

Страница 18: ...nty 5 13 INSTRUCTINGTHEUSER Hand over all documentation supplied with this appliance including these instructions and explain the importance of keeping them in a safe place Explain to the user how to...

Страница 19: ...condition of the entire flue assembly Compare the results with the appliance design specification Any deterioration in performance must be identified and rectified without delay Ensurebothflueventuris...

Страница 20: ...e electrical supply and attach a suitable manometer to the gas valve outlet test nipple Remove the compensator tube 7 3 1 SETTING THE MAXIMUM BURNER PRES SURE Light the boiler as described in 5 6 and...

Страница 21: ...omponents may also assist in locating the fault 7 7 3 POLARITYCHECK With the appliance connected to the electrical supply and using a suitable multimeter carry out the following voltage tests connect...

Страница 22: ...LS CN8 3 CN8 5 ON PCB NO NO YES MADE A LINK BETWEEN BLACK BLACK WIRES AT BOILER TERMINAL STRIP SWITCH ON BOILER AND SELECT MODE TO WINTER C H THERMOSTAT AT MAX YES LOOSE THE PUMP ACTING WITH A SCREWDR...

Страница 23: ...HECK SUPPLY FUSE CONNECTORS TO BOILER TERMINALS MAINS BLUE BROWN WIRES AT BOILER STRIP NO REPLACE WIRING OR CONNECTIONS TERMINAL STRIP AND CONTROL BOARD YES YELLOW LED BLINKS CHIMNEY SWEEPER CYCLE RES...

Страница 24: ...BETWEEN TERMINALS CN8 7 CN8 8 ON PCB NO YES NO CHECK WIRING AND CONNECTIONS NO DO THE AIR FLOW SWTCH TURN ON CHECK WIRING AND CONNECTIONS AIR FLOW SWITCH AND CONTROL BOARD YES NO ARE THE VENTURI TUBE...

Страница 25: ...AND SELECT MODE TO WINTER C H THERMOSTAT AT MAX START RESTART THE TEST NO NO YES REPLACE WIRE AND CONNECTIONS REPLACE CONTROL BOARD REPLACE MODULATOR COIL IS THE RESISTENCE OF MODULATOR COIL ABOUT 70...

Страница 26: ...R FLOW TEMPERATURE 80 C WAIT WATER FLOW TEMPERATURE 80 C NO YES REPLACE CONTROL BOARD REMOVE JUMPER IS TIMER JUMPER ON RESTART THE TEST DO BURNER AND FAN SWITCH ON OPEN THE LINK BETWEEN BLACK BLACK WI...

Страница 27: ...ressure switch T L High limit thermostat P A Water pressure switch S R Primary NTC sensor JP1 Jumper CH only JP2 Setting timer JP3 Natural gas or LPG selector JP4 Jumper disable enable DHW absolut the...

Страница 28: ...EGRALTIME CLOCK TheVokera integral time clock Part no 433 should be installed as shown in diagram 19B If a room thermostat is to be connected it should be of the voltage free type and must be con nect...

Страница 29: ...Ignition module 10022174 20 Printed Circuit Board 10025340 21 Led Light Guide 10023816 26 Instrumental panel 10027015 27 Knob 10023818 28 Knob 10023817 31 Case 10023822 40 Door panel 10023810 61 Cover...

Страница 30: ...lve 2907 23 Connection 10022499 27 Heating cock 1789 31 Venting plugs kit 01005137 63 Pipe 10020898 288 O ring 6898 289 Clip 2223 290 Clip 2165 300 Clip 2222 303 Connection 2217 353 Ogive 1824 400 Wir...

Страница 31: ...e 10023603 3 Pump 10024573 7 Pipe 10022000 8 Heat exchanger 10023651 9 Pipe 10022002 12 Washer 2226 201 Washer 5026 285 NTC sensor 8484 289 Clip 2223 290 Clip 2165 299 Washer 10022726 417 Limit thermo...

Страница 32: ...or manifold 10025271 4 Burner 10025270 5 Spark electrode 10025985 12 Pipe 10023996 13 Gas valve 10025074 14 Gas valve solenoid 10020838 15 Gas cock 10020897 16 Cover assembly 10024779 18 Glass 1002155...

Страница 33: ...Lateral insulating panel 2231 4 Front insulating panel 2232 10 Fan 10020793 12 Connection 10021972 20 Fumes testing connection pipe 10021973 25 Pressure differential switch kit 01005272 28 Stop clip 1...

Страница 34: ...e Thiswillensurethattheoutputoftheboiler burner pressure is not compromised due to a high flow temperature 10 5 2 SETTINGTHE MINIMUM BURNER PRESSURE Once the maximum burner pressure has been checked a...

Страница 35: ...33 Mynute 24m...

Страница 36: ...0 333 0520 Fax 01442 281403 After Sales Service Tel 0870 333 0220 Vok ra Ireland West Court Callan Co Kilkenny Tel 05677 55057 Fax 05677 55060 Vok ra Ltd reserve the right to change the specifications...

Отзывы: