background image

Supplied By www.heating spares.co  Tel. 0161 620 6677

23

7.2.5

HEATING MODE
With the selector switch in the ON position and any
additional controls (time clock, programmer, room
thermostat, etc,) calling for heat, the appliance will
operate in the heating mode. The pump and fan will
be activated via the flow temperature sensor. When
the fan is sensed to be operating correctly (tacho
signal), the ignition sequence commences. Ignition
is sensed by the electronic circuitry to ensure flame
stability at the burner. Once successful ignition has
been achieved, the electronic circuitry increases
the gas rate to 75% of the MAX Heating (set by the
corresponding HTG trimmer) for a period of 15
minutes. The speed of the fan and therefore the
output of the boiler is determined by the tempera-
ture of the water sensed by the flow temperature
sensor, consequently a high temperature at the
flow sensor results in a lower fan speed. As the
water temperature increases, the temperature
sensors – located on the flow pipe of the boiler –
reduce the fan speed via the electronic circuitry.
Depending on the load, either the water tempera-
ture will continue to rise until the set point is
achieved or the water temperature will fall whereby
fan speed will increase relative to the output
required. When the boiler has reached the set point
(+ hysterisis), the burner will switch off. The built-
in anti-cycle device prevents the burner from re-
lighting for approximately 3-minutes. When the
temperature of the flow sensor falls below the set
point (- hysterisis), the burner will re-light.
NOTE
If the spark/sensing electrode does not sense
ignition the appliance will re-attempt ignition a
further 4-times then go to lockout. When the set-
point has been reached (the position of the heating
temperature selector) as measured at the primary
thermistor, the appliance will begin the modulation
phase whereby the fan and gas valve will
continuously modulate to maintain the set-point.
If the temperature continues to rise and exceeds
the set-point by 5°C (hysterisis), the burner will
shut down. A new ignition sequence will be
enabled when the 3- minute anti-cycle has been
performed and the temperature at the primary
thermistor has dropped 5°C (hysterisis) below the
set-point.
NOTES
When the request for heating and/or hot water has
been satisfied, the appliance pump and fan may
continue to circulate to dissipate any residual heat
within the appliance.

7.3

APPLIANCE FAN SPEEDS
The appliance fan speeds require to be checked
and/or adjusted prior to making any adjustments
to the gas valve or if the main PCB has been
replaced.
ATTENTION
Gas type and appliance fan speed (output) must
be set 
according to the specific appliance
specification. Vokera accepts no responsibility if the
gas type and/or fan speed is not correctly adjusted
according to the respective appliance specification
as detailed on the appliance data badge.

7.3.1

CHECKING/ADJUSTING THE APPLIANCE FAN
SPEEDS
Move the selector switch to the OFF position and
remove the 3-selector knobs.

7.3.2

ABSOLUTE MAX FAN SPEED
Locate the MAX trimmer (fig. 32) and gently adjust
clockwise or counter clockwise to achieve the
correct fan speed (see table 7.3.6).
NOTE
The display shows the fan RPM in multiples of
1000, i.e. 2.5 = 2500RPM.

7.3.3

ABSOLUTE MIN FAN SPEED
Locate the MIN trimmer (fig. 32) and gently adjust
clockwise or counter clockwise to achieve the
correct fan speed (see table 7.3.6).
NOTE
The display shows the fan RPM in multiples of
1000, i.e. 2.5 = 2500RPM.

7.3.4

IGNITION FAN SPEED
ATTENTION
Do this operation only after the adjusting of
absolute max and min fan speed.
Locate the IGN trimmer (fig. 32) and gently adjust
clockwise or counter clockwise to achieve the
correct fan speed (see table 7.3.6).
NOTE
The display shows the fan RPM in multiples of
1000, i.e. 2.5 = 2500RPM.

7.3.5

HEATING FAN SPEED
Locate the HTG trimmer (fig. 32) and gently adjust
clockwise or counter clockwise to achieve the
correct fan speed (see table 7.3.6). speed (see
table 7.3.6).
NOTE
The display shows the fan RPM in multiples of
1000, i.e. 2.5 = 2500RPM.

Fig. 32

7.3.6

FAN SPEED TABLE
Use the following table to set the corresponding
fan speeds that are relative to the appliance you
are working on.

FAN SPEED (rpm) TABLE

MODEL

MAX

MIN

HTG

IGN

12HE

3.700

1.300

3.500

3.700

15HE

4.200

1.300

4.200

3.700

20HE

5.400

1.700

5.400

3.700

25HE

5.500

1.700

5.500

3.700

30HE

5.200

1.400

5.200

3.700

35HE

6.000

1.400

6.000

3.700

Содержание Mynute 12HE

Страница 1: ...Supplied By www heating spares co Tel 0161 620 6677 Installation Servicing Instructions THESEINSTRUCTIONS TO BE RETAINED BY USER 0694 0694BR1207...

Страница 2: ...ombustion analysis 16 5 8 Final flushing of the heating system 17 5 9 Setting the boiler operating temperature 17 5 10 Setting the system design pressure 17 5 11 Regulating the central heating system...

Страница 3: ...pump expansion vessel safety val ve pressure gauge and automatic by pass The Mynute HE range are produced as room sealed category II2H3P appliances suitable for internal wall mounting applications on...

Страница 4: ...ector clockwise to increase the boiler outlet temperature or counter clockwise to reduce the outlet flow temperature 2 digit LED display Displays the current outlet temperature of the boiler During a...

Страница 5: ...Ignition is sensed by the electronic circuitry to ensure flame stability at the burner Once successful ignition has been achieved the electronic circuitry increases the gas rate to 75 of the MAX Heati...

Страница 6: ...l 12HE 15HE 20HE 25HE 30HE 35HE Power consumption Watts 150 150 150 150 165 165 Supply V Hz 230 50 Internal fuse 3 15A T for PCB 3 15A F for connections block External fuse 3A 2 8 Flue Details concent...

Страница 7: ...re to the side of the vertical terminal 500 mm Q From the top of the vertical terminal to the roof flashing As determined by the fixed collar of the vertical terminal 2 11 PUMP DUTY Fig 3 shows the fl...

Страница 8: ...ipes must be fitted in accordance with BS 6891 Pipe work from the meter to the appliance must be of adequate size Pipes of a smaller size than the appliance gas inlet connection must not be used The i...

Страница 9: ...ke up vessel or tank must be fitted with an approved non return valve andstopcockforisolationpurposes Thefeedpipe should be connected to the return pipe as close to the boiler as possible 3 6 8 FREQUE...

Страница 10: ...gard for the damage and discoloration thatmayoccurtobuildingproductslocatednearby The terminal must not be located in a place where it is likely to cause a nuisance see I S 813 In cold and or humid we...

Страница 11: ...by using a double pole switch with a contact separation of at least 3 5mm 3 high voltage category The switch must only supply the appli ance and its corresponding controls i e time clock room thermost...

Страница 12: ...top of the carton pull both sides open do not use a knife unfold the rest of the carton from aroundtheappliance carefullyremoveallprotec tive packaging from the appliance and lay the accessories etc t...

Страница 13: ...flue system Connect the required number of flue extensions or bends up to the maximum equivalent flue length to the flue terminal see fig 7 8 The flue system should have a minimum of 1 maximum of 3 r...

Страница 14: ...or additional bend s connect the required number of flue extensions or bends up to the maximum equivalent flue length between the boiler and vertical flue assembly see fig 8 Ensure that any horizonta...

Страница 15: ...level with or below that of the exhaust pipe Depending on site conditions it may be preferable to install the terminal assembly prior to fitting the twin flue pipes Mark and drill a level 130mm hole f...

Страница 16: ...ety valve connection pipe and tighten The discharge pipe must have a continuous fall away from the appliance to outside and allow any water to drain away thereby eliminating the possibility of freezin...

Страница 17: ...minal block When connecting the EARTH wire ensure that it s left slightly longer about 2cm that the others this will prevent strain on the EARTH wire should the cable become taut Do not remove the lin...

Страница 18: ...from the lowest points Open the drain valve full bore to remove any installation debris from the boiler prior to lighting Refill the boiler and heating system as described in 5 3 5 5 PRE OPERATION CHE...

Страница 19: ...urn valves until the individual return temperatures are correct and are approximately equal 5 12 FINAL CHECKS ENSURE ALL TEST NIPPLES ON THE APPLIANCE GAS VALVE ARE TIGHT AND CHECKED FOR SOUNDNESS ENS...

Страница 20: ...REPLACEMENT OF COMPONENTS Although it is anticipated that this appliance will give years of reliable trouble free service the life span of components will be determined by factors such as operating c...

Страница 21: ...return inlet pipe Disconnect thermistor electrical plug Replace in the reverse order 6 11 PRINTED CIRCUIT BOARD fig 21 Carry out component removal procedure as described in 6 4 Pull the control fascia...

Страница 22: ...eck and adjust burner pressure settings WARNING A GAS SOUNDNESS CHECK MUST BE CARRIED OUT 6 13 ELECTRODES CONDENSE SENSOR fig 23 Carry out component removal procedure as described in 6 4 Unclip and re...

Страница 23: ...flue collector E The heat exchanger can now be lifted up and withdrawn from the appliance 6 18 EXPANSION VESSEL fig 1 Should the removal and replacement of the expansion vessel be deemed impractical...

Страница 24: ...rols have been designed to further increase fuel economy by ensuring the boiler remains in the modulation phase during any heating requests This reduces the amount of ON OFF periods and therefore incr...

Страница 25: ...3 minute anti cycle has been performed and the temperature at the primary thermistor has dropped 5 C hysterisis below the set point NOTES When the request for heating and or hot water has been satisf...

Страница 26: ...and integrity Symptom Possible cause No display ignition Check wiring check electrical supply No hot water Check external controls No heating Check external controls Fault code Possible cause 10 Chec...

Страница 27: ...on of the fault These series of checks must be carried out before attempting any faultfinding procedures on the appliance On completion of any task that required the disconnection and re connection of...

Страница 28: ...circulation around heating circuit s thermistors flowsensor temperature AL34 Fan tacho signal fault Final Reset check appliance operation check fan AL40 Insufficient system water pressure Final Check...

Страница 29: ...re that these controls do not inhibit or limit the response to any heat request from a DHW cylinder Contact the controls manufacturer and orVokera technical department should you require more specific...

Страница 30: ...see photos 36 37 and connectthe230wiringharnessasindicatedinthe figs 39 40 The programmer can be used with a typical S Plan or Y Plan controls arrangement as detailed in figures 39 40 IMPORTANT The bo...

Страница 31: ...stor NTC AD01A Main PCB CN1 CN5 Connection to PCB 230V X2 X16 Connection to PCB 24V F O H T Flow over heat thermostat H E T Heat exchanger thermostat M3 M5 Terminal strip for supply in clock room ther...

Страница 32: ...Blue Green Yellow Room Thermostat Cylinder Thermostat Boiler programmer connections Boiler programmer connections Wiring Centre or Junction Box CylinderThermostat green yellow blue brown orange grey...

Страница 33: ...10028559 10028559 10028559 10028559 10028559 31 Case assembly 10028432 10028432 10028432 10028448 10028451 10028451 40 Door panel 10028553 10028553 10028553 10028553 10028553 10028553 78 Cover assembl...

Страница 34: ...005137 01005137 01005137 63 Pipe 10020898 10020898 10020898 10020898 10020898 10020898 200 Washer 5023 5023 5023 5023 5023 5023 265 Washer 5236 5236 5236 5236 5236 5236 266 Washer 5237 5237 5237 5237...

Страница 35: ...28539 10028539 10026272 10026272 71 Pipe 10028430 10028430 10028430 10028430 10028515 10028515 72 Venting plug 01005137 01005137 01005137 01005137 01005137 01005137 73 Cock 10028431 10028431 10028431...

Страница 36: ...28424 10028206 10028206 46 Gas diaphragm 10020265 10020265 10020265 10027161 10027162 10027162 67 Washer 10026322 10026322 10026322 10026322 10026322 10026322 69 Tryton 10028425 10028425 10028425 1002...

Страница 37: ...6323 482 Washer 10026366 10026366 10026366 10026366 10026366 10026366 487 Washer 10026345 10026345 10026345 10026345 10026345 10026345 509 High limit thermostat 10026982 10026982 10026982 10026982 100...

Страница 38: ...umgasrate 0 27 0 27 0 39 0 47 0 54 0 54 kg hr Injectorsize 3 6 3 6 3 6 4 7 5 0 5 0 mm Efficiency SEDBUK 93 3 92 9 92 6 92 4 92 8 92 9 Band A Band A Band A Band A Band A Band A Emissions CO max mg kWh...

Страница 39: ...r fan speed is not correctly adjusted according to the respective appliance specifica tion as detailed on the appliance data badge 10 7 1 CHECKING ADJUSTINGTHEAPPLIANCEFAN SPEEDS Move the selector swi...

Страница 40: ...DUCER BEEN FITTED YES NO WHAT TYPE OF SCALE REDUCER HAS BEEN FITTED FOR THE DOMESTIC HOT WATER MODE MEASURE RECORD GAS RATE 3 hr MAXIMUM BURNER OPERATING PRESSURE IF APPLICABLE mbar COLD WATER INLET T...

Страница 41: ...MPANY NAME TEL No CORGI ID CARD SERIAL No COMMENTS SIGNATURE SERVICE 3 DATE ENGINEER NAME COMPANY NAME TEL No CORGI ID CARD SERIAL No COMMENTS SIGNATURE SERVICE 4 DATE ENGINEER NAME COMPANY NAME TEL N...

Страница 42: ...Supplied By www heating spares co Tel 0161 620 6677...

Страница 43: ...Supplied By www heating spares co Tel 0161 620 6677...

Страница 44: ...General Enquiries Tel 0870 333 0520 Fax 01442 281403 After Sales Service Tel 0870 333 0220 Vok ra Ireland West Court Callan Co Kilkenny Tel 05677 55057 Fax 05677 55060 Vok ra Ltd reserve the right to...

Отзывы: