HEC-Series Service Manual
ELECTRICAL CONTROLS & THEIR FUNCTIONS
10/21/01
6-2
Description of Control Panel Parts.
*BT1 and BT2.
Bin Thermostats.
Ice bin thermostats for automatically stopping and starting the
machine based on the ice level in the storage bin. BT1 (Crushed Ice). BT2 (Cylinder Ice).
C. Compressor Motor Contactor.
Provides power to the compressor motor. Energized during
freezing and thawing. Normally closed contact provides power to the compressor crankcase heater
when the machine is off.
P. Pump Contactor.
For making and breaking contacts to start and stop the circulating water
pump. Energized during the freeze, pumpdown, and clean modes.
CU. Cutter Contactor.
For making and breaking contacts to start and stop the cutter. Energized
during the harvest mode.
PLC. Programmable Logic Controller.
For monitoring, sequencing, and controlling various
functions of the Tube-Ice
®
operation. Also has a built in thaw timer for controlling the time of the
thawing period. Thawing time is adjustable from 1 1/2 to 5 minutes.
*FPS1 and FPS2. Freezer Pressure Switches.
For regulating the ice thickness by sensing the
freezer pressure and initiating the thaw period. FPS1 (Crushed Ice). FPS2 (Cylinder Ice).
*R. Reversing Relay.
Switches machine to either cylinder or crushed ice by making or breaking
various circuits concerning cylinder or crushed ice production. Energized during crushed ice
production only.
FC. Fan Contactor.
Cycles the fan motor(s) of air-cooled condenser “On” and “Off”. Activated by
the condenser pressure switch. (Air-cooled machines only).
SVI. Service Indicator Switch.
For disabling the machine and entering a troubleshoot mode to
identify a machine “fault”. Opened for entering a troubleshoot mode, closed for normal machine
operation.
FU0 through FU5.
Overload and short circuit protection of the components controlled by the PLC
output. See Wiring Schematics.
CD-OL. Compressor Motor Overload.
HEC-30 and HEC-40 only. Stops the machine in the
event of a mechanical or electrical malfunction of the compressor motor, causing excessive amperage.
Is automatically reset, but the machine must be manually restarted by the “Start” push button or will
automatically restart after two hours.
CD-TS. Compressor Motor Thermal Overload.
HEC-30 and HEC-40 only. Stops the machine in
the event of excessive temperature in the compressor motor windings. Will reset when motor cools
sufficiently. The machine can be manually restarted by the “Start” push button or will restart
automatically after the compressor stops when this overload trips and restarts. The machine will stop
by long freeze cycle “fault” after repeated overload trips.
HEC-10 and HEC-20 have built in motor overload protection with automatic reset.
*Note: Components used in dual ice type machines only.
Содержание HEC-10
Страница 1: ...HEC SERVICE MANUAL ...
Страница 12: ...HEC Series Service Manual INTRODUCTION 10 24 01 1 5 FIGURE 1 2A Assembly Model HEC 30 Air Cooled Front View ...
Страница 13: ...HEC Series Service Manual INTRODUCTION 10 24 01 1 6 FIGURE 1 2B Assembly Model HEC 30 Air Cooled Rear View ...
Страница 14: ...HEC Series Service Manual INTRODUCTION 10 24 01 1 7 FIGURE 1 2C Assembly Model HEC 30 Water Cooled Front View ...
Страница 15: ...HEC Series Service Manual INTRODUCTION 10 24 01 1 8 FIGURE 1 3B Assembly Model HEC 30 Water Cooled Rear View ...
Страница 45: ...HEC Series Service Manual INITIAL START UP AND OPERATION 10 21 01 5 4 FIGURE 5 2 Piping Schematic Air Cooled ...
Страница 46: ...HEC Series Service Manual INITIAL START UP AND OPERATION 10 21 01 5 5 FIGURE 5 3 Piping Schematic Water Cooled ...
Страница 95: ...HEC Series Service Manual SERVICE OPERATIONS 10 21 01 9 13 FIGURE 9 9 Cutter Water Tank Parts ...
Страница 96: ...HEC Series Service Manual SERVICE OPERATIONS 10 21 01 9 14 FIGURE 9 10 Cutter Drive Parts ...
Страница 97: ...HEC Series Service Manual SERVICE OPERATIONS 10 21 01 9 15 FIGURE 9 11 Cutter Parts ...
Страница 106: ...HEC Series Service Manual MODEL NUMBER STRUCTURE 10 21 01 10 1 10 Model Number Structure ...