HEC-Series Service Manual
SERVICE OPERATIONS
10/21/01
9-17
Pumping Down Freezer.
If it should become necessary to pump the refrigerant out of the freezer,
sufficient vapor should be retained to hold one pound of pressure in the freezer so that air will not
enter if the system is opened.
A total pumpdown is the first phase of the clean mode. Refer to Section 6, Total Pumpdown Mode
to perform this function. After the pumpdown is accomplished, push the “Clean” button to “Off” to
stop the water pump.
Note: After completing the total pumpdown cycle, the liquid line will remain full of liquid refrigerant
from the receiver “king” valve (58) to the liquid feed “A” solenoid valve (20).
If it becomes necessary to open freezer to the atmosphere, you will need to remove the remaining
refrigerant by using an approved refrigerant recovery unit. Isolate that part of the system by closing
the necessary hand stop valves at the receiver, condenser, compressor, etc. before using the recovery
unit and opening the system.
Pumping Down Entire System.
If it should become necessary to pumpdown the entire system,
including the liquid line, the following should be performed. Manually open the liquid feed “A”
solenoid valve (20) by backing the stem out. Close liquid outlet “king” valve (58) on the receiver
(15R). Put machine into total pumpdown as described above.
Removal Of Refrigerant From The Machine.
To transfer the refrigerant charge from the machine
into a separate container, proceed as instructed above under pumping down freezer. This will isolate
most of the refrigerant in the receiver and the recovery unit can be connected to the access port (44)
of the liquid outlet “king” valve (58) at the bottom of the receiver. Open the valve access port by
turning the valve stem in (front seat) and operate the recovery unit until the system is considered
empty.
! WARNING !
Approved recovery equipment, hoses, gages, and refrigerant containers must be
used to comply with all local and federal EPA regulations.
! WARNING !
! WARNING !
Follow these instructions carefully.
Severe personal injury can result from improper
discharge of refrigerant.
! WARNING !
! WARNING !
It is not recommended that refrigerant be transferred from a
refrigeration system into a cylinder. If such a transfer is made, the
refrigerant cylinder must be an approved CLEAN cylinder--
free of any contaminants or foreign materials--and must be weighed
continuously to assure contents do not exceed net weight specified
by cylinder manufacturer or any applicable code requirements.
! WARNING !
Содержание HEC-10
Страница 1: ...HEC SERVICE MANUAL ...
Страница 12: ...HEC Series Service Manual INTRODUCTION 10 24 01 1 5 FIGURE 1 2A Assembly Model HEC 30 Air Cooled Front View ...
Страница 13: ...HEC Series Service Manual INTRODUCTION 10 24 01 1 6 FIGURE 1 2B Assembly Model HEC 30 Air Cooled Rear View ...
Страница 14: ...HEC Series Service Manual INTRODUCTION 10 24 01 1 7 FIGURE 1 2C Assembly Model HEC 30 Water Cooled Front View ...
Страница 15: ...HEC Series Service Manual INTRODUCTION 10 24 01 1 8 FIGURE 1 3B Assembly Model HEC 30 Water Cooled Rear View ...
Страница 45: ...HEC Series Service Manual INITIAL START UP AND OPERATION 10 21 01 5 4 FIGURE 5 2 Piping Schematic Air Cooled ...
Страница 46: ...HEC Series Service Manual INITIAL START UP AND OPERATION 10 21 01 5 5 FIGURE 5 3 Piping Schematic Water Cooled ...
Страница 95: ...HEC Series Service Manual SERVICE OPERATIONS 10 21 01 9 13 FIGURE 9 9 Cutter Water Tank Parts ...
Страница 96: ...HEC Series Service Manual SERVICE OPERATIONS 10 21 01 9 14 FIGURE 9 10 Cutter Drive Parts ...
Страница 97: ...HEC Series Service Manual SERVICE OPERATIONS 10 21 01 9 15 FIGURE 9 11 Cutter Parts ...
Страница 106: ...HEC Series Service Manual MODEL NUMBER STRUCTURE 10 21 01 10 1 10 Model Number Structure ...